Technical data
MENV-MINI4-02 Issue2 June 2006
11
SECTION 3 – ENGINEERING OPTIONS
General
The panel has various options which are programed by the selection of DIL switches. This section
explains which switch relates to which option.
DIL SWITCHES ON MASTER PCB, PCMINI4
Switch Function when ‘off’ Function when ‘on’
1 Faults non latching Faults latch. Press Reset to clear
2 Short circuit = fault, all zones Short circuit = fire, all zones
3 Detector removal, by Schottky diode
method, all zones
Zener diode head removal, Hochiki YBO-R-5ZD
or Apollo 45681-350, all zones
4 Aux contacts operate for all zones No aux contacts for zone 4
5 Sounders activate for all zones No sounders operate for zone 4
6 Sounders continuous for zone 4 Sounders pulse for zone 4
7 Zone 4, latching fire Zone 4, non latching fire
8 Activate controls code = 1234 Activate controls code = 2411