Temporal Horns and Horn-Strobes
During installation, the Horn is configured for steady or temporal tone signal. When temporal
output is selected, all Horns on a common two-wire circuit are self-synchronized. Integrity Series
Horns emit a low frequency “growling” tone that demands attention. Horns can be configured for
either high output (98 dBA) or low output (94 dBA); and are listed for outdoor use.
757-1A-T (Red) 757-1A-TW (White) Temporal Horn Catalog Sheet: 85001-0341
757-7A-T (Red) 757-7A-TW (White) Temporal Horn-Strobe, 15/75cd Catalog Sheet: 85001-0341
757-8A-T (Red) 757-8A-TW (White) Temporal Horn-Strobe, 110cd Catalog Sheet: 85001-0341
4" Square Box Mount Strobes
405 Series strobes are self-synchronized to flash at one fps across their full operating voltage range.
UL 1971 synchronization requirements are achieved when used with the G1M Signal Master (see
page 38). Strobes must be connected to signal circuits that output a constant (not pulsed) voltage.
A diode is used to allow full signal circuit supervision. 405 Series strobes are suitable for outdoor use
and installed to a standard four-inch square electrical box.
405-5A-T (Red) 405-5A-TW (White) Strobe - 15 cd Catalog Sheet: 85001-0305
405-7A-T (Red) 405-7A-TW (White) Strobe - 15/75 Catalog Sheet: 85001-0305
405-3A-T (Red) 405-3A-TW (White) Strobe - 30 cd Catalog Sheet: 85001-0305
405-6A-T (Red) 405-6A-TW (White) Strobe - 60 cd Catalog Sheet: 85001-0305
405-8A-T (Red) 405-8A-TW (White) Strobe - 110 cd Catalog Sheet: 85001-0305
CS-405-7A-T (15/75 cd) CS-405-8A-T (110 cd) Strobe - Weatherproof (red) Catalog Sheet: 85001-0305
Re-Entrant Speakers and Speaker-Strobes
Re-entrant speakers feature a sealed, high efficiency compression driver that’s both weatherproof
and vermin proof. This makes them ideal for public places and outdoor areas such as parking garages
and transport terminals. All Integrity speakers include a DC Blocking Capacitor that permits electrical
supervision of the audio distribution circuit. Models for 25VRMS and 70VRMS circuits are available.
757-1A-R25 (Red) 757-1A-R25W (White) 25 V Re-entrant Speaker Catalog Sheet: 85001-0317
757-7A-RS25 (Red) 757-7A-RS25W (White) 25 V Re-entrant Speaker-Strobe, 15/75cd Catalog Sheet: 85001-0317
757-3A-RS25 (Red) 757-3A-RS25W (White) 25 V Re-entrant Speaker-Strobe, 30cd Catalog Sheet: 85001-0317
757-8A-RS25 (Red) 757-8A-RS25W (White) 25 V Re-entrant Speaker-Strobe, 110cd Catalog Sheet: 85001-0317
757-1A-R70 (Red) 757-1A-R70W (White) 70 V Re-entrant Speaker Catalog Sheet: 85001-0317
757-7A-RS70 (Red) 757-7A-SS70W (White) 75 V Re-entrant Speaker-Strobe, 15/75cd Catalog Sheet: 85001-0317
757-3A-RS70 (Red) 757-3A-RS70W (White) 75 V Re-entrant Speaker-Strobe, 30cd Catalog Sheet: 85001-0317
757-8A-RS70 (Red) 757-8A-RS70W (White) 75 V Re-entrant Speaker-Strobe, 110cd Catalog Sheet: 85001-0317
Enhanced Integrity Series
Harsh Environment
Signals
All Enhanced Integrity devices are UL 1971 listed for both wall and ceiling
orientation. Enhanced Integrity strobes meet the latest UL1971 synchronization
requirements when used with the G1M Signal Master (see page 40). Integrity
devices are shipped with wall mount style “FIRE” lens markings. Other lens