Specifications
24
EST3
EST3
Network
SUBMIT
Network
Ground Fault Detection Module
The GFD module is designed to detect
ground fault conditions on either of two
independent power or data circuits. Each
circuit must be balanced with respect to
ground. The module will detect when the
resistance between any of the monitored
conductors and earth ground drops be-
low 10 K Ohms. Two LEDs are provided to
indicate the conductor with the ground
condition. A normally energized Trouble/
Ground Fault relay is provided with
NO/NC relay contacts for interfacing
with monitoring systems.
GFD Ground Fault Detection Module Catalog Sheet 85010-0115
From 24Vdc on
firealarm panel
Toearth ground
Polarity is not important
Pair one in
Pair one out
Pair two in
Pair two out
To supervisory module
(i.e. Signature Series
CT1 or CT2 module) or
3-IDC traditionalzone
card.
+
+
+
+
arth
D
Power
Circuitpair 1 Circuitpair 2
II
P1
D1 D2
T
3-2-1
T
Trou le F Contacts
CC
13
1
1
3
1114
2
11
4
12
Alphanumeric Pager Interface
The API-8/232ME is an interface between
alarm and monitoring equipment and per-
sonal pager systems or PCS messaging
services. The interface ensures that key
personnel, regardless of their location, are
notified of EST3 status changes. The unit
can monitor an ASCII text string from a
serial printer port for eight different event
types. Each event type is defined by one
or two programmable keywords up to 20
characters in length.
API-8/232ME Paging System Interface with programming software Catalog Sheet: 85006-0045
LINE
BATTERY
POWER
~~
COMMON
1 234 5678
PHONE
SILENCE
INPUTS
TROUBLE
SYSTEM
RESET
SERIAL
PORTIN
SERIAL
PORT OUT
(PROGRAM)
NC
COM
NO
INPUT STATUS LEDS
1 234 5678
PWR
LINE
CALL
BUSY
PAGE
DATA
LOAD
TRBL
To Telephone Line
To Telephone
Interface Trouble
Contacts
ToOptional12 VDC
Standby Battery
ToPrinter Portof
InitiatingSystem
NOorNCDry Contact Input
or
0 to 48 VDC Input Signal
RS-232 Input
To24VAC/DC
OptionalNO Reset Switch
ToOptionalNO
Trouble Silence Switch
Communications Bridge
The 3-SM8051-0139 Communication Bridge converts the EST3 External Communications
Protocol (ECP) to a variety of commercial protocols that facilitate one-way and two-way
communications between EST3 and other in-building systems and sensors using a common
protocol via an Ethernet LAN.
3-SM8051-0139 Communications Bridge Catalog Sheet: 85010-0119
3-SM8700-07 BacNet® Driver - ArcNet (Includes ArcNet Card) Catalog Sheet: 85010-0119
3-SM8700-19 Driver, Metsys N2 Catalog Sheet: 85010-0119
3-SM8704-02 BacNet Driver - Ethernet Dedicated Catalog Sheet: 85010-0119
3-SM8700-39 EST Driver Catalog Sheet: 85010-0119
8051-01-ESTPROG Custom Programming Catalog Sheet: 85010-0119