Specifications
15
ENVISION COMMERCIAL SPECIFICATION CATALOG
Envision Controls - Premier cont.
DIP Switch Settings
Prior to powering unit, ensure that all DIP switches on SW2 & SW3 are set properly according to the tables below.
FACTORY SETUP DIP SWITCHES (SW3)
DIP 
SWITCH 
NUMBER
DESCRIPTION OFF POSITION ON POSITION
SW 3- 1
Dual Capacity/Single-Speed
Configures the control for single-speed compressor operation or dual capacity 
operation.
Dual Capacity
Operation
Single-Speed Operation
SW 3- 2
Zoned/Finish on Second Stage
This switch allows the unit to down stage with the thermostat when off and finish 
with second stage when on. Finish on second stage reduces stage changing in 
reciprocating dual capacity compressors.
Normal - All Other 
Systems
Finish on 2nd - Unzoned 
Dual Capacity E Series or 
Premier 2 Speed
SW 3- 3
No RPM/RPM
Configures the control to monitor the RPM output of an ECM/ECM2 blower motor. 
When using IntelliZone or a PSC blower motor, the control should be configured for 
“NO RPM” sensing.
PSC Blower/RPM 
Monitoring Disabled
ECM-ECM2 Blower/RPM
Monitoring Enabled
SW 3- 4
Electric heat and ECM2 
Allows backward compatibility with older P Series. In the Off position this switch 
allows older electric heat board (17P501A01) and older ECM (square end) compat-
ibility. On is for all newer EH board (17P514A01) and ECM2 (round end).
Old EH & Old ECM Normal
SW 3- 5
On dual capacity units this switch allows stage change: on the fly when off, and 1 
minute delay when on. A delay is required on all reciprocating dual capacity units.
Envision E Series or P Series
FACTORY SETUP DIP SWITCHES (SW3)
DIP 
SWITCH 
NUMBER
DESCRIPTION OFF POSITION
ON POSITION
SW 2- 1
Service Test Mode 
On the control, allows field selection of “NORMAL” or “TEST” operational 
modes. Test mode accelerates most timing functions 16 times to allow faster 
troubleshooting. Test mode also allows viewing the “CURRENT” status of the fault 
inputs on the LED display.
Test Mode Normal Speed Operation
SW 2- 2
Freeze Detection Sensing
This DIP switch allows field selection of low source water thermistor fault sensing 
for well water (30°F) or antifreeze-protected (15°F) earth loops.
Loop Water Freeze 
Detection 15° F
Well Water Freeze 
Detection 30° F
SW 2- 3
Accessory Relay
Allows field selection of the accessory relay to operate with the compressor or 
blower.
Acc Relay
Tracks Blower
Acc Relay
Tracks Compressor
SW 2- 4
Blower Speed Control 
Allows field selection of reduced blower speed (85% of selected medium and high 
speed – ECM only) for cooling in the dehumidification mode.
Dehumidification 
Blower Speeds
Normal Blower Speeds
SW 2- 5
Auxiliary Off
Disables 3rd-stage Heating. Full emergency heat would still be available if needed.
Disable Heating 
Stage 3
Enable Heating 
Stage 3
SW 2- 6
Diagnostics Inputs
Allows viewing the inputs from the thermostat to the control board such as Y1, Y2, 
O, G, W, SL1-In on the LED display.
Diagnostic Inputs 
Viewed at LEDs
Normal Display
Viewed at LEDs
SW 2- 7
Diagnostics Outputs
Allows viewing the outputs from the control board such as compressor, reversing 
valve, blower, hot water pump, and loop pump on the LED display.
Diagnostic Outputs 
Viewed at LEDs
Normal Display
Viewed at LEDs
SW 2- 8
Thermostat Selection 
Configures the control for a pulsed lockout signal (ComforTalk and FaultFlash 
thermostats) or continuous 5 VAC lockout signal.
Pulsed “L” signal Continuous “L” signal