Installation manual
22
ENVISION SERIES INSTALLATION MANUAL 
The Envision series comes with a holding charge. The charge must be adjusted in the eld based on performance. 
Refrigeration piping on the split consists of installing a brazed copper line set between the blower coil unit and the unit’s split 
compressor section. To select the proper tube diameters for the installation, refer to the table on page 9. Line sets over 60 
feet long are not recommended because of oil return and pressure drop problems. The suction line must always be insu-
lated. Handle and route the line sets carefully to avoid kinking or bending the tubes. If the line set is kinked or distorted and 
it cannot be formed back into its original shape, the bad portion of the pipe should be replaced. A restricted line set will affect 
the performance of the system.
Connection to Air Coil
Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and 
maximum length. As in all R-410A equipment, a reversible liquid line lter drier is required to insure all moisture is removed 
from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be 
insulated with a minimum of 1/2” closed cell insulation. All insulation should be painted with UV resistant paint or covering to 
insure long insulation life. 
Fasten the copper line set to the blower coil unit as instructed by the coil installation instructions shown in Figure 14. 
Nitrogen should be bled through the system at 2 to 3 PSI to prevent oxidation inside the refrigerant tubing. Use a low silver 
phos-copper braze alloy on all brazed connections.
Braze line set to the service valve stubs on the 
inside front of the split cabinet as shown in Figure 
13. Nitrogen should be bled through the system at 
2 to 3 PSI to prevent oxidation contamination. Use 
a low silver phos-copper braze alloy on all brazed 
connections. Envision split units are shipped with 
a factory charge and service valves are not to be 
opened until the line set has been leak tested, 
purged and evacuated. Schrader cores should be 
removed before brazing. A heat sink should be used 
on the service valves and TXV to prevent damage 
caused by excessive heat.
Refrigeration
Replace caps after
opening system
Service ports for
attaching refrigerant
gauges
Insulated
Suction Line
Braze
Connection
Liquid
Line
ccw
ccw
Figure 13: Typical Split System Refrigerant Line Connections
Position Description System
Service
Port
 CW - Full In  Shipping Position Closed Open
 CCW - Full Out 1/2 turn CW  Service Position Open Open
 CCW - Full Out  Operation Position Open Closed
TXV ("IN" toward condensing unit)
Equalizer
Bulb
Suction
Liquid
TXV has internal check valve
Figure 14: Attaching the Air Coil










