Installation manual
21
ENVISION SERIES INSTALLATION MANUAL
DIPSWITCH
NUMBER
DESCRIPTION OFFPOSITION ONPOSITION
SW1 N/A NOTUSED N/A N/A
SW2
1
Service/TestMode-Allows control of “NORM” or “TEST” opera-
tional modes. Test mode accelerates most timing functions 16 
times to allow faster troubleshooting. Test mode also allows view-
ing the “CURRENT” status of the fault inputs on the LED display.
Test Norm
2
LowSourceWaterTemperatureLimit(WaterFlow)
This lockout mode occurs when the low source water thermistor 
temperature is at or below the selected point (well 30°F or loop 15°F) 
for 30 continuous seconds.
Loop 
(Protection 15° F)
Well 
(Protection 30° F)
3
AccessoryRelay
Allows eld selection of the accessory relay to operate with the 
compressor or fan.
Fan Comp
4 NOT USED N/A N/A
5 NOT USED N/A N/A
6
InputDiagnostics-Allows viewing the inputs from the thermo-
stat to the control board such as Y1, Y2, O, G, W, SL1-In on the 
LED display.
Diagnostic Inputs 
viewed at LEDs
Normal Display 
viewed at LEDs
7
OutputDiagnostics-Allows viewing the outputs from the control 
board such as the compressor, reversing valve, blower, hot water 
pump, and loop pump on the LED display.
Diagnostic
Outputs viewed at 
LEDs
Normal 
Display viewed
at LEDs
8
ThermostatSelection 
Congures the control for a pulsed lockout signal (ComforTalk and 
FaultFlash thermostats) or continuous 5 VAC lockout signal.
Pulsed “L” 
signal
Continuous “L” 
signal
SW3
1 Single or Dual Capacity Operation Dual Cap 1 Speed
2
Zoned/FinishonSecondStage
This switch allows the unit to down stage with the thermostat 
when off and nish with second stage when on. Finish on second 
stage reduces stage changing in reciprocating dual capacity 
compressors.
Normal - 
All other systems
Finish on 2nd 
Unzoned Dual 
Capacity 
E-Series or 
Premier 2 speed
3 ECM Fan Monitoring - Set for No PRM on split systems No RPM RPM
4 NOT USED N/A N/A
5
On dual capacity units this switch allows stage change: on the y 
when off, and 1 minute delay when on. A delay is required on all 
reciprocating dual capacity units.
Envision
E-Series or 
Premier
DIP Switch Settings