Installation manual

13
5 SERIES 500RO11 INSTALLATION MANUAL
Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor Ext
Loop
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC RLA LRA LRA*
026
208-230/60/1 187/253 18.2 11.6 58.3 21.0 5.4 17.0 19.9 30
038
208-230/60/1 187/253 23.8 15.2 83.0 30.0 5.4 20.6 24.4 40
049
208-230/60/1 187/253 33.0 21.1 104.0 37.0 5.4 26.5 31.8 50
064
208-230/60/1 187/253 42.3 27.1 152.9 54.0 5.4 32.5 39.3 70
072
208-230/60/1 187/253 46.3 29.6 179.2 63.0 5.4 35.0 42.4 75
4/3/13
Rated voltage of 208-230/60/1.
HACR circuit breaker in USA only.
All fuses Class RK-5
* With optional IntelliStart