ENVISION AIR HANDLER INSTALLATION MANUAL
Condensate Drain
To facilitate condensate removal, the air handler should 
be pitched 1/4” towards the drain in both directions. The 
drain line contains cold water and should be insulated in 
unconditioned spaces to avoid drain line condensation 
from dripping on ceiling, etc. The drain pan has a primary 
and auxiliary drain connection. The air handler drain 
connections must be connected to a drain line and pitched 
away from the unit a minimum of 1/8” per foot to allow 
the condensate to flow away from the air handler. A trap 
must be installed in the drain line below the bottom of the 
drain pan to ensure free condensate flow (units are not 
internally trapped). The primary condensate drain must 
be terminated to an open drain or sump. Do not connect 
the condensate drain to a closed waste system. An open 
vertical air vent should be installed to overcome line length, 
friction and static pressure. It is recommended that the 
auxiliary drain be connected to a drain line for all units. 
The auxiliary drain should be run to an area where the 
homeowner will notice it draining. The drain line should not 
be smaller than the drain connection at the condensate pan.  
If the air handler is located in an unconditioned space, water 
in the trap may freeze. It is recommended that the trap 
material be of a type that will allow for expansion of water 
when it freezes. Drain lines must be in conformance with 
local codes.
Air Handler Configuration
The Envision Air Handler is factory configured for upflow 
and horizontal left hand air discharge installation (Figure 1).  
For bottomflow or horizontal right hand discharge, certain 
field modifications are required.
Warning: Do not lift or reposition the ‘A’ coil by grasping 
the copper tube header or distributor. This could cause a 
tubing fracture resulting in a refrigerant leak.
General Installation Information cont.
Figure 1 - Factory configuration is top discharge and
horizontal left hand air discharge.
#
!