air handler User's Manual
6
ENVISION SERIES AIR HANDLER INSTALLATION MANUAL
Bottomflow Application
To convert the NAH series air handlers for bottomflow ap-
plications follow the steps shown below:
Remove all access panels. Disconnect the blower 
  harnesses from the motor and loosen ground wire from 
  blower. Remove the blower by removing 2 screws from 
  the blower mounting bracket, and slide the blower
  assembly out the front. Remove the stiffener bracket in
  front of coil, 'A' coil/pan assembly and the horizontal 
  drain pan. This will lighten the cabinet and make it easier 
 to maneuver.
Rotate the cabinet 180° from the upright position so that 
  the discharge air opening is located at the bottom and 
  the return air opening is at the top.
Install the blower assembly into the blower discharge 
  opening at the bottom of the cabinet by sliding the 
  blower mounting bracket under the discharge support 
  bracket and secure in place with 2 screws. The blower 
  harness and motor ground wire should be reattached 
  before sliding the blower into place.
On the NAH042-060 install the NAHBC bottomflow 
  conversion kit per instructions in the kit. Failure to install 
  this kit will result in condensate blow-off from the 'A' 
  coil into the cabinet and ductwork. 
Install the 'A' coil into the upper section of the cabinet 
  as pictured in Figure 2. Attach the stiffener bracket into 
  the two holes provided in the cabinet so that the bracket 
  is in front of the coil. The horizontal drain pan is not 
  needed and must be discarded. Plug the 2 drain hole 
  openings in the access panel with the plugs provided.
Replace the access panels.
Bottom air discharge units require the supply air opening 
  to be cut at least a 1/2” larger than the unit’s air outlet.
When installed on combustible flooring, protect the 
  edges of the floor opening with sheet metal over wrap or 
  other non-combustible material.
Bottom air discharge units should be sealed well to the 
  floor to prevent air leakage.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Horizontal Right Air Discharge 
Application
To convert the NAH series air handlers for horizontal right 
air discharge applications follow the steps shown below
Remove all access panels. Remove the stiffener bracket 
  in front of the coil, ‘A’ coil assembly and the horizontal 
 drain pan.
From the vertical upflow position, rotate the top of the 
  cabinet 90° to the right and set in place.
Remove the support bracket mounted to the top plate of 
  the ‘A’ coil. Rotate the ‘A’ coil support bracket 180° from 
  its original position and re-attach into existing holes in 
  the top plate of the coil. This must be done to prevent 
  the ‘A’ coil from falling into the drain pan (Figure 3).
Move the horizontal drain pan from the left side of the ‘A’ 
  coil to the right hand side of the ‘A’ coil. Place the ‘A’ coil 
  and horizontal drain pan assembly into the cabinet 
  so that the support bracket is resting in the horizontal 
  drain pan as shown in Figure 3. Attach the stiffener 
  bracket into the two holes provided in the cabinet so that
  the bracket is in front of the coil. 
Remove the 2 drain plugs from the upper right of the 
  access panel and install them on the lower left of the 
  access panel. Replace the access panels.
If the unit is suspended, the entire length of the cabinet 
  should be supported.
Important: When removing the coil, there is possible dan-
ger of equipment damage and personal injury. Be careful 
when removing the coil assembly from the unit.
1.
2.
3.
4.
5.
6.
Figure 2 - Bottomflow NAH.
Figure 3 - Horizontal Right Hand Air Discharge
Rotate the coil support bracket to this position
General Installation Information










