air handler User's Manual
11
ENVISION SERIES AIR HANDLER INSTALLATION MANUAL
Hydronic Models
Flow gpm
Pressure Drop (PSI)
40°F 50°F 60°F 100°F 110°F 120°F 130°F
3.0 0.5 0.5 0.5 0.4 0.4 0.4 0.4
4.5 0.9 0.9 0.9 0.8 0.8 0.8 0.8
6.0 1.4 1.4 1.4 1.2 1.2 1.2 1.2
9.0 2.8 2.6 2.5 2.4 2.4 2.4 2.3
12.0 4.6 4.4 4.2 4.0 4.0 4.0 3.9
15.0 7.0 6.8 6.6 6.0 6.0 5.9 5.8
Water Presure Drop - Hydronic Coil
Entering Water Temperature °F
EAT °F 100 110 120 130 140 150
65
44% 56% 69% 81% 94% 106%
70
37% 50% 63% 75% 87% 100%
Coil Capacity vs. Entering Water Temperature
Electrical Data
All field wiring must comply with local and national fire, 
safety and electrical codes. Be sure the available power is 
the same voltage and phase as that shown on the unit serial 
plate. Refer to the unit Electrical Data table for fuse and cir-
cuit breaker sizing. The thermostat should be connected to 
the air handler and to the compressor section. Line voltage 
power should be supplied to the breakers on air handlers 
with 15kW and 20kW heater kits (see the electric heat 
control section picture). On air handlers with no electric 
heat installed, or with 5kW and 10kW heater kits the power 
should be supplied to L1 and L2 lugs on PB (see air handler 
control section picture). 
Air Handler Control Section:
Power should be supplied to PB on air handlers with no 
electric heat and 5kW or 10kW heaters.
Electric Heat Control Section:
Power should be supplied to the breakers on air handlers 
with 15kW and 20kW heaters.










