HIGH WALL COOLING DUCTLESS 9,000, 12,000, 18( 24,000 ......
mNSTALLATION, OPERATION AND MAINTENANCE P/N 240006537, MANUAL Rev. 1.0 [01/07] This manual is intended as an aid to a qualified service personnel for proper installation, operation, and maintenance of EMI EnviroAir high efficiency R-410A Ductless Split Systems. Carefully read these instructions before attempting installation or operation.
oMain System Breaker: Sized per unit requirements, to be mounted adjacent to outdoor unit. o Mounting Hardware: condenser pad. Wall anchors, o Vacuum Pump oGauge Set: R-410 specific. o High Vo#age interconnect Wiling: TheEnviroAir system isanefficient duct- 14 AWG wiring from outdoor unit to inlesssplitairconditioning system withcooF door unit for power and control. * ingcapacities from9,000-24,000 Btuhand heatpumpcapacity of9,000-24,000 Btuh.
KWCA09A0 K1CA9000A00 Cooling Only 9,000 115zlz60 KWCA12A0 K1CA2000A00 Cooling Only 12,000 115zl-60 KWCA18D0 K1CA8000D00 Cooling Only 18,000 208/230-1-60 KWCA24D0 K1CA4000D00 Cooling Only 24,000 208/230-1z60 KWHA09A0 K1 HA9000A00 Heat Pump 9,000 115-1-60 KWHA12A0 K1 HA2000A00 Heat Pump 12,000 115-1-60 KWHA18D0 K1HA8000D00 Heat Pump 18,000 208/230zl-60 KWHA24D0 K1HA4000D00 Heat Pump 24,000 208/230-1-60 Example EnviroAir Unit Unit Style W = High Waft Unit Duty C = Cool
Determine the best location for mounting the indoor unit, it must be located a minimum of 4 ft (6 ft or more recomended) from the floor and no less than 6" from ceiling. Pay attention to the air circulation in the room, 9,000 & 12,000 Btuh units throw air 15ft, 18,000 & 24,000 Btuh units throw air 25ft, ensure no obstacles to airflow exist. Locate the indoor and outdoor units as close together as possible, maximum line set run and lift MUST NOT BE EXCEEDED.
structions, failureto followI s maycausepossible mat=I ndvoidanywarranty. J J Remove indoor and outdoor units from the carton/box, indoor unit carton contains, remote controt and batteries, ensure these are kept in a safe place during installation. Locate area to install indoor unit the unit should be located a minimum of 6 ft. from the floor and 6" from the ceiling. Choose an area where the watt is plumb and determine how to best to run the unit interconnects.
Prepare the evaporator for moundng by removing the mounting bracket from the rear of the indoor unit. Use a Phillips head screwdriver to remove the unit pipe strap. If the unit is a heat pump the defrost sensor also must be undone from its retainer. If mounting the unit on an outside wall measure from the edges of the unit to the center of the line set 90 ° bend to locate the the center of the wall penetration. Drill a 3" e hole through the wall.
_are unit fine set connections Rotate refrigerant line stubs gently to 90 ° (if mounting on an outside wall). For other line set configurations align the stubs as required. ieP: Use Duct tape to tape the Con-_ nsate hose (make sure it is below I the Line set stubs) and the defrost I sensor (heat pump only).
Install unit on mounting bracket Feed the line set stubs/condensate hose/ wiring connections through a o 3" hole in the walt. Position the evaporator so that the "key" slots on the back of the unit slide onto the tabs on top of the mounting bracket. Then push the lower portion of the evaporator against the bracket until it latches into the mounting bracket. indoor unit is now installed, it should be ptumb, level and flush with the wait.
Re_nt Line Set Pi in interconnectingline set between the outdoor unit and the indoor unit, must have both refrigerant lines insulated as the expansion device is located in the outdoor unit. Gently bend the tine set stubs from the indoor unit to the desired location. Using 2 x 10"/12" Crescent wrenches remove the flare nuts from the indoor unit tine stubs. The indoor unit is filled with a dry gas, check for retease of this to ensure that no leaks are present.
Evacuation Gauges can now be attached to the service ports - SERVICE PORTS HAVE A 5/16" CONNECTION TO GAUGES, which is different from the norm for R-22. You will need specific hoses or an adaptor for the 5/16" connection. Once the gauges are attached the line set can be leak checked using Nitrogen at 300 psig. Evacuate the unit and interconnect down to a minimum of 400-500 Microns, break vacuum with Nitrogen to further leak check.
Electrical Wifin_ installation Electrical Wiring should be done by a certified electrician in accordance with aft National ElectdcaICode (NEC) and local state!city building codes. ALL CONTROLS WIRING BETWEEN INDOOR AND OUTDOOR UNIT IS HIGH VOLTAGE MINIMUM 14 AWG WIRE MUST BE USED. Remove terminal covers from indoor unit and wire to the terminals, (small screwdriver required). Control wiring from the Control wiring at outdoor unit (cooling only).
If the system is a heat pump the defrost sensor must be connected from the indoor unit to the defrost sensor in the outdoor unit. Standard lead length is 25 ft, if a longer length is required then cut the lead and extend using thermostat wire. ote: use of colored wire (supplied with_ Illne set) and defrost sensor connected I (_eatpump only). .... The heat pump defrost sensor interconnect wire comes bundled up with the indoor units.
12) Condensate Hose: The unit is provided with approximately 18" of condensate hose connected. Hose connection is sized to accept a 3/4" OD or 5/8" ID clear plastic hose to then extend to building drain. There is approximately 6' of additional drain hose supplied with the (accessory) line set. With the evaporator and line set completely evacuated the system can now be opened to allow the refrigerant charge in the outdoor unit to be released into the line set.
Start the indoor unit, cooling mode is only allowed when the outside ambient temperature is above 60 ° F to prevent damage to the compressor. Unit has a 3 minute time delay before the compressor start up operation. ote: tf interconnect is less then 12_ eta small amount of refrigerant may I ed to be reclaimed to achieve the I oper charge for optimal operation.
Instrucdons: 1. Measure suction pressure and determine evaporator-refrigerant temperature on R410A scale of low-side gauge. 2. Measure suctionqine temperature on suction line of the unit. 3. Measure outdoor and indoor temperatures. 4. Determine from the table what the superheat should be for the indoor and outdoor temperatures. 5. Adjust charge if needed. Be sure unit is running at stabilized condition.
Guide to features and their function There are many models, features and appearance will vary. The figure shown is representative of the operation of 9,000/12,000 Btuh systems. Takesinthe Ak returnindoorair grill ] A_e tnl÷t a__de_ & ea_ su_a_e Pushdown the air inletgrilleandthe pushbothsides ofak inlet grilleat the bottom.
Remote Contro| Operation /o ON!OFF button ) This button,when pressed,starts operation and stops whenpressedagain (:SETTEMPERATUREbutto_ FAN SWING button
Remote _._. Centre| Note: Selecting Operation Wait 3 minutes before restarting the unit. MODE of OPERATION To select operating mode, point the remote control toward the indoor air conditioning unit: 1) Press the ON/OFF @ 2) Press the MODE O operating modes: button to START. button to step through the _' AUTO MODE - automatically operates the system in DRY, COOL ,or HEAT mode depending on the indoor temperature and setting.
Remote Centre| Operation _erature _'uetment in AUTO SELECT mode To adjust the air temperature during AUTO SELECT mode, point the remote control toward the indoor air conditioning unit: 1) Press the _ button once. To raise the set point temperature 1°C or 1°F. 2) Press the button once, to reduce the set point temperature 1°C or 1°F. COOL/HEAT & FAN/DRY mode Point the remote control toward the indoor air conditioning unit: 1) Press the ON/OFF @ button.
Remote Centre| Operation Up/down air flow direction adiustment The up/down air flow direction can be adjusted by pressing the VANE CONTROL button on the remote control, each time this button is pressed, the vane angle changes in the following (1) _ sequence:(2) !_ _ (3) JT (4) i (5) , (1) through (5) are fixed positions. , AUTO oscillates up and down automatically. Air flow veleeit_iustment To change the vane control velocity press the FAN SPEED button.
Remote Centre| Operation Setting the time When batteries are inserted, the time will automaticafly be set to 12.00 AM. ( 1) With the back cover off, press the CLK button with the tip of a ball pen, etc. The time indicator win flash, the time can now be set. 2) Press the HOUR button to change the hour. Example: (Set to IO:AM ) see front view. 3) Press the MIN button to change the min= utes. Example: (Set to 30) see front view. 4) When time is set press the CLK button again.
Remote Centre| Operation How to set _he ON diner 1) Press the AUTO START button to set the ON timer mode during operation. Each time the button is pressed, the ON timer mode alternates between ON and OFR 2) Set the time on the timer using the HOUR and MIN buttons. Each time the HOUR button is pressed, the timer hours are increased by 1 hour. Each time the "MIN" button is pressed, the timer minutes are increased by 10 minutes. 3) To release the ON timer, press the AUTO START button again.
Features of Heating Operations Heating operation will cease at ap= proximately 15° F outdoor tempera= ture due to a sensor located in the outdoor unit. This product does not contain supplemental electric heat, therefore other means of heat need to used when this system ceases opera= tion at low outdoor ambients. Basic _les and #erformances The Heat Pumps absorb heat from the outdoor air and transfers it indoors to heat the indoor air.
Guide to features and their function Takesinthe indoorair Air return grHI ,, Pushdownthe airinletgrilleand the pushbothsidesof air inletgrille at the bottom. Lightlypush bothsidesof the airinlet grilleat the bottonandpull it to this sidetill a resistanceis felt. Note: TiI _ tl¢#_8aI bI ussd as 8_ ett_t[j_f_¢_ ¢SIIS_=IIt to tutI OI[01ff US _,v!en _x_s_'_o_e _,xx¢o le_b _e av,a lable Do not open the grille at an angle over 60 degrees. .
Remote I Centre| Operation setthis lightis ft Air conditionerrunninglight II C081ill@IIy Fa_ s#*e# ._______. ..... rllolel_ll indieaio_ In2="j__E=_=.J L__]............... L............ .[L......... ,,. f¢ o.: •o.......4... t. , _ ' Q DDh $_i_l%temp{{rata_e o_fT_i;l_e_ ............................................... ¢J_@ ]rllctt llllIe 111t_1 abestio_(indics'l_¢ _ ) Digital display / it canshowset pointtemperature,fixedtime [or ma functon code.
Remote Centre| Operation MODE I_l¢_Wos_eb_bv3flapr_,_de ONIOFFbutton This buttoc whenpressed,sta4s operation and stops whenpressedagain SLEEP bu_bn FAN SPEEDbutton ] _0 IN FLAP bu{bn STOP huron This bufbn is usedfor selectionof the leffkightair flow direction,wheneverpressedthe flap changes from osculatingto fix, or fromfixedto osculating CLK butbn NOTE When air-conditioneriscool-onlymodel,the HEAT modeis bypassedto FANmode When ea@ huron on the remote _ntroiler is p_'essedwi{h the iemote contr
Remote _- Control Note: Selecti_a Operation Wait 3 minutes before restarting the unit. MODE of OPERATION To select operating mode, point the remote control toward the indoor air conditioning unit: 1) Press the ON/OFF ('D 2) Press the MODE O operating modes: button to START. button to step through the AUTO MODE - automatically operates the system in DRY, COOL ,or HEAT mode depending on the indoor temperature and setting.
Remote Centre| Operation Tem#erature adiuetment in AUTO SELECT mode To adjust the air temperature during AUTO SELECT mode, point the remote control toward the indoor air conditioning unit: 1) Press the 1°C or 1°F. button once, to raise the set point 2) Press the \./button once, to reduce point temperature 1°C or 1°F. the set COOL/HEAT & FAN/DRY mode Point the remote control toward the indoor air conditioning unit: 1) Press the ON/OFF ,_ button.
Remote Centre| Operation U_ & down air flow direction adiuetment The up/down air flow direction can be adjusted by pressing the OUT FLAP button on the remote control, each time this button is pressed, the vane angle changes in the following sequence: (1) _ (2) _ j (4) _ (5) , . (1) through (5) are fixed positions. , AUTO oscillates up and down automatically. Air flow veleeit_uetment To change the vane control velocity press the FAN SPEED button.
Remote Centre| Operation Setdn¢_ the time r clock button flashing ---'gack ...................... Front When batteries are inserted, the time wifl automaticafly be set to 12:00 AM. 1) With the back cover off, press the CLK button with the tip of a ball pen, etc. The time indicator will flash, the time can now be set. 2) Press the HOUR button to change the hour. Example: (Set to IO:AM ) see front view. tess I L.... 3) Press the MIN button to change the mira utes.
Remote Centre| Operation How to $et the ON timer 1) Press the AUTO START button to set the ON timer mode during operation. Each time the button is pressed, the ON timer mode alternates between ON and OFR 2) Set the time on the timer using the HOUR and MIN buttons. Each time the HOUR button is pressed, the timer hours are increased by 1 hour.
Features of Heating Operations proximately !5 ° F outdoor temperature e to a sensor located in the outdoor unit. portant: Heating operation will cease is product does not contain supplemenI tal electric heat, therefore other means of I heat need to used when this system ceas_,,_soperation at low outdoor ambients. _ei lee and erformaneee , The Heat Pumps absorb heat from the outdoor air and transfers it indoors to heat the indoor air.
Maintenance To clean the surface of the air conditioner: Use a soft and dry cloth to wipe the air conditioner off, or use a vacuum cleaner to clean it. , if the air conditioner is very dirty, use a damp soft cloth with a neutral household detergent to clean the surface of the unit. f"NNote: If the air filter screen is blocked_ by dust or dirt, the performance of cooling and heating will be affected, and the operation noise and power consumption will increased.
Basic Operation Characteristics_ The unit can not be restarted just after shut down. (RUN light is on) Restart is detayed for 3 minutes after shut down to protect the unit. Three=minute protection timer incorporated in the microcomputer actuates automatically Except when power is connected, this function does not actuate. Air does not blow out at starting of heat= ing operation. Air circulation is stopped to prevent blowing cold air into the room until heat exchanger warms up.
Phone: 1-800-228-9364 Fax: 1-800-232-9364 O_',_#_"__2' _ ,_(_',' _ 5780 Success Drive, Rome, NY 13440