Owner`s manual
Figure 19. Non-Combustible Clearances
mantLe & non-combustibLe cLeaRances:
4
5
8
"
(417mm)
Distance from a side wall
42"
(1067mm)
49"
(1245mm)
Unit can be placed on the floor
12" (305mm)
Mantle
2" (51mm)
Mantle
When installing the Q2 as a zero clearance replace the correct clearances and materials must be used:
aboVe unit: A minimum 10” of non-combustible facing material, with a R-Value no less than 0.26, must
be used above the unit (in front of the included steel framing plate).
in fRont of unit:
aDjacent/siDewaLL: There must be a minimum distance of 4 5/8” (417mm) from the side of the Q2
cabinet to an adjacent wall composed of combustible material (see Figure 19).
mantLe: It is not necessary to install a mantle, but if one is desired the guidelines as shown in Figure 19
Initial Installation
QUALIFIED INSTALLERS ONLY
16