INSPECTION & START-UP CHECKLIST
Receiving & Inspection
Unit Received Undamaged
Unit Received Complete As Ordered
Unit Arrangement/Hand Correct
Unit Structural Support Complete & Correct
Handling & Installation
Unit Mounted Level & Square
Proper Access Provided For Unit & Accessories
Proper Electrical Service Provided
Proper Overcurrent Protection Provided
Proper Service Switch/Disconnect Provided
Proper Hot Water Line To Unit
Proper Chilled Water Line Size To Unit
Proper Steam Line Sizes To Unit
Proper Refrigerant Line Sizes To Unit
Proper Steam Supply Pressure To Unit (15psi Max)
Proper Steam Condensate Trap On Return Line
All Shipping Screws & Braces Removed
All Services To Unit In Code Compliance
Cooling/Heating Connections
Protect Valve Package Components From Heat
Mount Valve Packages
Connect Field Piping To Unit
Pressure Test All Piping For Leaks
Install Drain Line & Traps As Required
Insulate All Piping As Required
Install Condensate Pan Under Piping As Required
Ductwork Connections
Install Ductwork, Fittings & Grilles As Required
Proper Supply & Return Grille Type & Size Used
Control Outside Air For Freeze Protection
Insulate All Ductwork As Required
Electrical Connections
Refer To Unit Wiring Diagram
Connect Incoming Power Service or Services
All Field Wiring In Code Compliance
Unit Startup
General Visual Unit & System Inspection
Record Electrical Supply Voltage
Record Ambient Temperature
Check All Wiring For Secure Connections
Close All Unit Isolation Valves
Flush Water Systems
Fill Systems With Water/Refrigerant
Vent Water Systems As Required
All Ductwork & Grilles In Place
All Unit Panels & Filters In Place
Start Fans, Etc.
Check For Overload Condition Of All Units
Check All Ductwork & Units For Air Leaks
Balance Air Systems As Required
Record All Final Settings For Future Use
Check Piping & Ductwork For Vibration
Check All Dampers For Proper Operation
Verify Proper Cooling Operation
Verify Proper Heating Operation
Reinstall All Covers & Access Panels
Blower / Motor
Check Sheave Set Screw Tightness
Check / Adjust Sheave Alignment
Check Blower Wheel Set Screw Tightness
Check / Adjust Belt Tension
Adjust Blower Speed as Necessary for Balancing Airow