Specifications
4" (100mm)
Exhaust Tube
4" (100mm)
Vent Pipe
Wall Thimble
45
o
 Elbow or 
Termination Cap
High Temperature RTV 
Silicone Required
3" (80mm)
Inlet Tube
Installation
horizontal exhauSt through Wall inStallation:
A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces, 
or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired, 
the installation must conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and 
Equipment and with all  local  regulations, including those  referring to regional  and national. Only use 
venting of L or PL type with an inside diameter of 4 inches (100 mm).
1. Place the appliance 15” (37.5 cm) away from the wall. If the stove is to be set on a hearth pad, set 
the unit on it. 
2. Locate the center of the exhaust pipe on the stove. Extend that line to the wall. Once you have located 
the center point on the wall, refer to pellet vent manufacturer installation instructions for correct hole 
size and clearance to combustibles.
3. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour 
barrier in accordance with local building codes.
4. Install  a  length  of  vent  pipe  into  the  wall  thimble.  Try  not  to  have  joints  inside  the  thimble.               
 The pipe should install easily into the thimble.
5. Connect  the  exhaust  vent  pipe  to  the  exhaust  pipe  on  the  stove.  Seal  the  connection  with  high 
temperature silicone.
6. Install the fresh air intake (see 
Outside Fresh Air COnneCtiOn).
7.  Push the stove straight back, leaving a minimum of 4” (10 cm) clearance from the back of the stove 
to the wall. Seal the vent pipe to the thimble with high temperature silicone.
Figure 12: Straight through wall Installation. 
12