Operating instructions
Installation
4. Using the template make the block-
off plate of 24 gauge or thicker steel.
Drill two (2) holes in each ange for
mounting the plate.
5. Mount the block-off plate using
masonry screws in a masonry
replace and sheet metal screws on a
zero-clearance replace (screws need
only be long enough to penetrate the
rst layer of metal).
6. Insulate the block-off plate using high
- temperature berglass insulation
and furnace cement.
7. After installing the unit into place and
the pipe through the block-off plate,
use high - temperature berglass
insulation and furnace cement to seal
any gaps between the pipe and block-
off plate (allow the cement to dry for
at least 24 hours before burning).
Figure 19: Insert Install into a Zero-Clearance Fireplace.
Fig. 20: Masonry Fireplace Direct Connection Insert
20
Mantel
Surround Panel
USA 16” (406 mm)
CND 18” (450 mm)
Block-off plate or
damper adaptor.
Stainless steel chimney
connector must extend
12" (305mm) past the
block-off plate.
Damper must
be removed
Zero-clearance
(metal) firebox
Masonry Fireplace
Mantel
Damper removed
or fastened open
Surround Panel
USA 16” (406 mm)
CND 18” (450 mm)
Block-off plate or
damper adaptor.
The stainless steel
chimney connector
must extend 12"
(305mm) past the
block-off plate.
Zero Clearance Notes:
The replace must not be altered, except for the exceptions below. The
permanent metal warning label provided must be attached to the back of the
replace, stating that the replace may have been altered to accommodate
the insert, and must be returned to original condition for use as a conventional
replace. The following modication of factory built
replaces are permissible: removal of damper, removal
of smoke shelf or bafe, removal of ember catches,
removal of re grate, removal of viewing screen/curtain,
and removal of doors. The factory built chimney must be
listed per UL 127 (US), and meet type HT requirements
of UL 103 (US). Factory built replace chimneys tested
to UL 127-1998, may be at the replace manufacturer’s
option, tested to the same criteria as UL 103 HT
requirements. If the chimney is not listed as meeting HT
requirements, or if the factory built replace was tested
prior to 1998, a full height listed chimney liner must be
installed from the appliance ue collar to the chimney top.
The liner must meet type HT requirements (2100°F) per
UL 1777 (US). The liner must be securely attached to the
insert ue collar and the chimney top. To prevent room
air passage to the chimney cavity of the replace, seal
either the damper area around the chimney liner with high
temperature sealant or the replace front with berglass
batting.