Specifications
11
OPERATING INSTRUCTIONS 
Control Board Functions (continued) 
Auger Trim: This is used to change the feed rate on the minimum heat level for various 
quality of pellet fuel. This will help to keep the flames from extinguishing on the 
minimum heat level setting. It is also used to lower heat output on the minimum heat 
level setting. 
Push and release the Auger Trim button until the heat level 1 and 5 lights appear. This 
will slightly increase the feed rate on the minimum heat level setting to keep the burn pot 
flames from going out.  
Push and release the button until the heat level 1 and 4 lights appear, this will reduce the 
pellet feed rate on the minimum heat level setting. Use this setting to reduce the heat 
level output on low. 
Push and release the button until just the heat level 1 setting light is on, this is the factory 
setting and works for most types of fuel. 
Figure 3      Control Panel 
Open Door 
If the door is opened, while the unit is operating, it 
must be closed within 30 seconds or the unit will go 
into vacuum error mode. If this happens, close the 
door, turn the control panel switch to "OFF" then 
back to the setting it was previously at. 
Refueling 
For maximum performance we recommend that you 
do not let the hopper drop below 1/4 full. KEEP 
LID CLOSED AT ALL TIMES EXCEPT WHEN 
REFILLING. DO NOT OVERFILL HOPPER. 
Safety Features
1.  Your unit is equipped with a "high 
temperature limit" thermo snap disc. This 
snap disc serves to shutdown the auger in 
the case of an over temperature situation 
(such as convection fan failure). This disc 
has a manual reset button that will have to 
be reactivated once the unit has cooled 
down. 
2.  If the combustion fan malfunctions a 
vacuum switch will automatically shut down 
the auger (see also Open Door section 
above). 
If either of these situations occur contact your dealer as a service call may be 
required. 