10. VENTING 
VENT TERMINATION CLEARANCES 
A= Clearance above grade, verandah, porch, deck, or 
[balcony (*12 inches (30cm) minimum] 
B= Clearance to window or door that may be opened  [*12 
inches (30cm) minimum] 
C= Clearance to permanently closed window [minimum 12 
inches (30cm) recommended to prevent condensation on 
window] 
D= Vertical clearance to ventilated soffit located  above 
the terminal within a horizontal  distance of 2 feet (60cm) 
from the center-line  of the terminal [24 inches ( 60cm) 
minimum] 
E= Clearance to unventilated soffit [18 inches  (45cm) 
minimum] 
F= Clearance to outside corner [12 inches minimum] 
G= Clearance to inside corner [ 12 inches minimum] 
H= *Not to be installed above a meter/regulator assembly 
within 3 feet (90cm) horizontally from the center-line of 
the regulator 
I= Clearance to service regulator vent outlet [*6 feet  (1.8m) 
minimum] 
J= Clearance to non-mechanical air supply inlet to building or 
the combustion air inlet to any  other appliance [12 
inches (30cm) minimum] 
K= Clearance to a mechanical air supply inlet [*6  feet 
(1.8m) minimum] 
L= *** Clearance above paved side-walk or paved driveway 
located on public property [*7 feet  (2.1m) 
minimum] 
M= Clearance under verandah, porch, deck, or balcony [*24 
inches (60cm) minimum **] 
*** A vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves 
 both dwellings ** 
 Only permitted if verandah. Porch, deck, or balcony, is fully open on a minimum of 2 sides beneath the floor 
•  As specified in CGA B149 Installation Codes (1991) Note: Local Codes or Regulations may require different clearances 