Unit installation

MAC 10
®
LEDC
4x4 Fan Filter Unit
8 Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance
Installation & Service Manual
CONTROL MODES
The ENV1028 operates in one of three selectable modes. The Mode is selected using DIP Switch S1.
MANUAL control, on-board potentiometer
ANALOG control, Remote 0-10 VDC
NETWORK control, MODBUS RTU
1
2
ON ADE02
1 3 4 5 6 7 8
O
N
2
1
2
ON ADE02
1 3 4 5 6 7 8
O
N
2
1
2
ON ADE02
1 3 4 5 6 7 8
O
N
2
Manual Mode = 1 OFF 2 OFF
Analog Mode = 1 ON 2 OFF
Network Mode = 1 OFF 2 ON
1
2
ON ADE02
1 3 4 5 6 7 8
O
N
2
Network Mode = 1 ON 2 ON
Note: Network mode can be congured using either DIP switch setting shown above.
DIP switch pictorials are for reference and may be labeled differently by the manufacturer.