COMMUNICATION SPECIFICATIONS
Overview:
MODBUS RTU protocol over RS485 (serial)
9600 baud rate, word length is 8, parity is none(n), stop bits=1
255 unique address values selectable by S2 switch settings
(recommended network node capacity 200 nodes)
Slew rate limited transceivers for improved network performance MODBUS Register Summary Table
DO NOT USE CROSSOVER CABLES. THIS MAY DAMAGE THE CONTROL CARD OR RENDER IT NON-OPERATIONAL.
MODBUS Register Specications:
Register Name R/W Values & Defaults Units Origin Comments
1 RUN/STOP RW 0,1 1 RAM power up from REG 14
2 DEMAND RW 0-100 % RAM power up from REG 10
6 SPEED R 0,5-2000 RPM LIVE
7 ANA1 R 0-1000 - LIVE Onboard Pot 0-1000=0-100%
9 STATUS R see detail - LIVE
10 DEFAULT SPEED RW 0-100 50 EEPROM applies to network only
12 CURRENT SPEED R 0-100 - LIVE
14 DEFAULT RUN/STOP RW 0,1 1 EEPROM applies in network mode only
24 ANA2 R 0-1000 - LIVE 0-10V input 0-1000=0-10VDC
To reset non-volatile registers to factory default values, write 170 (AA hex) to Register 14, and then cycle power.
Note: Register 24 may be read in network mode to determine the value of 0-10VDC signal that may be connected.
For example, a pressure transducer may be connected to indicate unit interal static pressure.