5. Door Lock Connecons
Mul Door Staons Wiring: 1. Internal Power Supply Mode
A. Connecon for Power-on-to-Unlock type:
B. Connecon for Power--off-to-Unlock type:
Use the power of the system to supply for the electronic lock, so that the lock can be
connected to the door staon directly, without an addional power supply for the
electronic lock. Note that the door staon can only output 12Vdc power, therefore the
kind of lock is limited.
• The rated power of the lock must be less than 12Vdc 300mA when using internal
power supply mode.
• The GND must connect to the negave of the lock, and the COM connect to the
posive .
• Jumper set to 1-2 posion for Power-off-to-Unlock safety type
(Normally closed mode); set to 2-3 posion for Power-on-to -Unlock type
(Normally open mode ).
• If different unlocking me is needed to be configured, change the Unlock Timing on
door staon.(In debug state,press [1 #] --> [1] Installer Setup--> [2]Unlock Timing)
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
ID Code=2
ID Code=3
ID Code=0
ID Code=1
85~260VAC
DPS
PS5
Code=4, DIP-6=on
CALL
UNLOCK
TALK/MON
IN-USE
Code=3, DIP-6=on
Code=2, DIP-6=on Code=1, DIP-6=on
CALL
UNLOCK
TALK/MON
IN-USE
CALL
UNLOCK
TALK/MON
IN-USE
CALL
UNLOCK
TALK/MON
IN-USE
1 2 3
654
7 8 9
#0
*
1 2 3
654
7 8 9
#0
*
1 2 3
654
7 8 9
#0
*
1 2 3
654
7 8 9
#0
*
JP_LK
12V 300mA
Jumper set to 2-3 posion
+
-
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
1
2
3
Set to Normally open on
the Unlock Relay mode
Set to Normally Closed on
the Unlock Relay mode
12V 300mA
Jumper set to 1-2 posion
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
+
-
JP_LK
1
2
3