5. Door Lock Connecons
Mul Door Staons Wiring: 1. Internal Power Supply Mode
A. Connecon for Power-on-to-Unlock type:
B. Connecon for Power--off-to-Unlock type:
Use the power of the system to supply for the electronic lock, so that the lock can be
connected to the door staon directly, without an addional power supply for the
electronic lock. Note that the door staon can only output 12Vdc power, therefore the
kind of lock is limited.
• The rated power of the lock must be less than 12Vdc 300mA when using internal
power supply mode.
• The GND must connect to the negave of the lock, and the COM connect to the
posive .
• Jumper set to 1-2 posion for Power-off-to-Unlock safety type
(Normally closed mode); set to 2-3 posion for Power-on-to -Unlock type
(Normally open mode ).
• If different unlocking me is needed to be configured, change the Unlock Timing on
door staon.(In debug state,press [1 #] --> [1] Installer Setup--> [2]Unlock Timing)
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
ID Code=2
ID Code=3
ID Code=0
ID Code=1
85~260VAC
DPS
PS5
Code=4, DIP-6=on
CALL
UNLOCK
TALK/MON
IN-USE
Code=3, DIP-6=on
Code=2, DIP-6=on Code=1, DIP-6=on
CALL
UNLOCK
TALK/MON
IN-USE
CALL
UNLOCK
TALK/MON
IN-USE
CALL
UNLOCK
TALK/MON
IN-USE
1 2 3
654
7 8 9
#0
*
1 2 3
654
7 8 9
#0
*
1 2 3
654
7 8 9
#0
*
1 2 3
654
7 8 9
#0
*
JP_LK
12V 300mA
Jumper set to 2-3 posion
+
-
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
1
2
3
Set to Normally open on
the Unlock Relay mode
Set to Normally Closed on
the Unlock Relay mode
12V 300mA
Jumper set to 1-2 posion
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
+
-
JP_LK
1
2
3