SecureStack C2 Redundant Power Supply Chassis C2RPS-CHAS2 Installation Guide C2RPS-CHAS2 Caution: Do not use this product with SecureStack PoE devices. Any SecureStack device with a “P” suffix in the model number (C2xxxx-xxP) indicates a SecureStack PoE-compliant device and is not compatible with this power system Precaución: El RPS no es compatible con switches SecureStack C2 con PoE.
Electrical Hazard: Only qualified personnel should perform installation procedures. Advertencia eléctrica: Solamente personal calificado debe realizar procedimientos de instalacion. Elektrischer Gefahrenhinweis: Installationen sollten nur durch ausgebildetes und qualifiziertes Personal vorgenommen werden. Notice Enterasys Networks reserves the right to make changes in specifications and other information contained in this document and its web site without prior notice.
Regulatory Compliance Information Federal Communications Commission (FCC) Notice This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a class A digital device, pursuant to Part 15 of the FCC rules.
Electromagnetic Compatibility (EMC) This product complies with the following: 47 CFR Parts 2 and 15, CSA C108.8, 89/336/EEC, EN 55022, EN 61000‐3‐2, EN 61000‐3‐3, EN 55024, AS/NZS CISPR 22, VCCI V‐3. Compatibilidad Electromágnetica (EMC) Este producto de Enterasys cumple con lo siguiente: 47 CFR Partes 2 y 15, CSA C108.8, 89/336/EEC, EN 55022, EN 55024, EN 61000‐3‐2, EN 61000‐3‐3, AS/NZS CISPR 22, VCCI V‐3.
Declaration of Conformity Application of Council Directive(s): Manufacturer’s Name: Manufacturer’s Address: European Representative Address: Conformance to Directive(s)/Product Standards: Equipment Type/Environment: 89/336/EEC 73/23/EEC Enterasys Networks, Inc. 50 Minuteman Road Andover, MA 01810 USA Enterasys Networks, Ltd.
Enterasys Networks, Inc. Firmware License Agreement BEFORE OPENING OR UTILIZING THE ENCLOSED PRODUCT, CAREFULLY READ THIS LICENSE AGREEMENT. This document is an agreement (“Agreement”) between the end user (“You”) and Enterasys Networks, Inc.
3. APPLICABLE LAW. This Agreement shall be interpreted and governed under the laws and in the state and federal courts of the Commonwealth of Massachusetts without regard to its conflicts of laws provisions. You accept the personal jurisdiction and venue of the Commonwealth of Massachusetts courts.
8. AUDIT RIGHTS. You hereby acknowledge that the intellectual property rights associated with the Program are of critical value to Enterasys and, accordingly, You hereby agree to maintain complete books, records and accounts showing (i) license fees due and paid, and (ii) the use, copying and deployment of the Program.
viii
Contents About This Guide Who Should Use This Guide ................................................................................................................ xi How to Use This Guide ........................................................................................................................ xi Related Documents ............................................................................................................................ xii Conventions Used in This Guide ....................
Tables 2-1 2-2 A-1 A-2 A-3 A-4 x Contents of C2RPS-CHAS2 Carton.......................................................................................2-2 Contents of C2RPS-PSM Carton ...........................................................................................2-2 C2RPS-CHAS2 Specifications.............................................................................................. A-1 C2RPS-PSM Specifications ..................................................................................
About This Guide This guide provides an overview, installation and troubleshooting instructions, and specifications for the Enterasys Networks™ SecureStack C2 redundant power supply chassis (C2RPS‐CHAS2), power supply module (C2RPS‐PSM), DC power cables (C2RPS‐PSM Cable), and AC power cords. Note: In this document, the following terms are used: • RPS refers to a complete redundant power system, which includes a C2RPS-CHAS2 chassis and optional power supply modules.
Related Documents This preface provides an overview of this guide and the SecureStack C2 manual set, and a brief summary of each chapter, and the conventions used throughout this guide. To locate information in this guide, refer to the following table: For... Refer to... The features and capabilities of the C2RPS-CHAS2 chassis and optional power supply modules. This chapter also provides the instructions for obtaining help from Enterasys Networks, if needed.
Conventions Used in This Guide Conventions Used in This Guide The following conventions are used in this guide: Note: Calls the reader’s attention to any item of information that may be of special importance. Caution: Contains information essential to avoid damage to the equipment. Precautión: Contiene información esencial para prevenir dañar el equipo. Achtung: Verweißt auf wichtige Informationen zum Schutz gegen Beschädigungen.
Conventions Used in This Guide xiv About This Guide
1 Introduction This chapter provides a functional overview of a Redundant Power System (RPS). For information about... Refer to page...
C2RPS-CHAS2 Chassis C2RPS-CHAS2 Chassis The chassis is a two‐slot frame without AC power connections or electronics. The chassis can be installed in a standard 19‐inch rack and populated with one or two PSMs. Each PSM operates independently. Figure 1‐1 shows the front view of the chassis without PSMs. Figure 1‐2 and Figure 1‐3 show the front and rear views of a fully populated chassis.
C2RPS-PSM Power Supply Module C2RPS-PSM Power Supply Module The C2RPS‐PSM provides the following: • Hot swap capability. • One 12 Vdc, 150 Watts of maximum‐continuous power output to a connected SecureStack C2 switch device. • Front panel Status LED that indicates if the PSM is operating correctly. Figures 1‐4 and 1‐5 show the front and rear view of the C2RPS‐PSM.
RPS Deployment Strategies RPS Deployment Strategies The RPS can be deployed in a variety of situations with mission‐critical applications. For example: • For use in a voice and data network where switches are connected to IP phones and PCs. Connecting an RPS to the switches can prevent voice network failures caused by switch power failures. • For use in traditional data 10/100/1000 Ethernet switches carrying mission‐critical data.
Getting Help Getting Help For additional support related to the C2RPS‐CHAS2 or this document, contact Enterasys Networks using one of the following methods: World Wide Web http://www.enterasys.com/support Phone 603-332-9400 1-800-872-8440 (toll-free in U.S. and Canada) For the Enterasys Networks Support toll-free number in your country: http://www.enterasys.com/support/gtac-all.html Internet mail support@enterasys.com To expedite your message, please type [C-SERIES] in the subject line.
Getting Help 1-6 Introduction
2 Installation Electrical Hazard: Only qualified personnel should perform installation procedures. Riesgo Electrico: Solamente personal calificado debe realizar procedimientos de instalacion. Elektrischer Gefahrenhinweis: Installationen sollten nur durch ausgebildetes und qualifiziertes Personal vorgenommen werden. This chapter provides instructions to install all the components of an RPS. To correctly install an RPS, follow the order of information listed below. For information about... Refer to page...
Installing C2RPS-PSMs 3. Perform a visual inspection of the switch devices for any signs of physical damage. Contact Enterasys Networks if there are any signs of damage. Refer to “Getting Help” on page 1‐5 for details.
Installing C2RPS-PSMs Figure 2-1 C2RPS-PSM Installation S2 HA S-C RP C2 r we Po à À  1 C2RPS-CHAS2 chassis 2 C2RPS-PSM power supply module SM S-P RP C2 à Á 3 Chassis power supply slot 4 Captive screws (2) Replacing an Installed C2RPS-PSM To replace a PSM installed in an operating system, proceed as follows: Caution: Observe all Electrostatic Discharge (ESD) precautions when handling sensitive electronic equipment.
Installing C2RPS-CHAS2 into the Rack Note: If you plan to remove and not replace a C2RPS-PSM, immediately reinstall coverplates over any empty power supply slots to prevent EMI leakage from the chassis. To install a PSM, proceed as follows: 1. Align the PSM with the slot, then slide the PSM forward until its front panel is flush against the chassis front panel. 2. Fasten the PSM to the chassis using the captive screws. 3. Perform steps 1 and 2 for each PSM being replaced.
Installing C2RPS-CHAS2 into the Rack Caution: To ensure proper ventilation and prevent overheating, leave a minimum clearance space of 10.16 cm (4.0 in.) at the front and rear of the N-POE Chassis. Precaución: Para asegurar una buena ventilación y evitar que el sistema se sobrecaliente, deje un espacio mínimo de 10.16 cm (4 pulgadas.) con respecto a la parte delantera y trasera del chasis N- POE.
Connecting the PSM Cables and AC Power Cords Connecting the PSM Cables and AC Power Cords The PSMs are connected to the SecureStack C2 Ethernet switch devices using C2RPS‐PSM Cables. To connect the PSMs, proceed as follows: 1. Connect one end of the C2RPS‐PSM Cable (shown in Figure 2‐3) to the Redundant Power Supply connector on the switch device. Then connect the other end to the Redundant Power Supply connector at the rear of the PSM as shown in Figure 2‐4 and Figure 2‐5. 2.
Connecting the PSM Cables and AC Power Cords Figure 2-5 C2RPS-PSM Cable and AC Power Cord Connections Redundant Power Supply STACK UP AC LINE 100-240 VAC 50-60 Hz 0.8 A MAX STACK DOWN MAC ADDRESS SERIAL NO. Ã À Á Â Redundant Power Supply Å AC LINE 100-240 VAC 50-60 Hz 2A MAX Ä 1 Switch device 2 PSM cable 3 PSM Redundant Power Supply connector 5.
Connecting the PSM Cables and AC Power Cords 2-8 Installation
A Specifications This appendix includes specifications for the C2RPS‐CHAS2, C2RPS‐PSM, 12‐Vdc power supply output connector, and provides the Compliance Standards. For information about... Refer to page... C2RPS-CHAS2 Chassis Specifications A-1 C2RPS-PSM Specifications A-2 C2RPS-PSM Redundant Power Supply Output Connector A-2 Compliance Standards A-3 Enterasys Networks reserves the right to change the specifications at any time without notice.
C2RPS-PSM Specifications C2RPS-PSM Specifications Refer to Table A‐2 for the input/output port specifications. Table A-2 C2RPS-PSM Specifications Item Specification Electrical AC Input Frequency Range 47–63 Hz AC Input Voltage Range 85–264 Vac Output Voltage 12 Vdc Output Current 1.0 A min., 8.5 A or 13.0 A max. Maximum Output Power 102 W or 156 W continuous Physical Dimensions 19.6 H x 5.2 W x 25.7 D (cm) 7.7 H x 2.04 W x 10.1 D (in.) Net Weight (Unit Only) 1.75 kg (3.
Compliance Standards Table A-3 C2RPS-PSM Redundant Power Supply Connector Pin Functions Pin Number Function 1 Ground 2 No connection 3 12 Vdc Output 4 12 Vdc Output 5 12 Vdc Output 6 12 Vdc Output 7 Ground 8 Ground 9 No connection 10 No connection 11 Status 1 12 Status 2 13 Power good 14 Ground Compliance Standards The C2RPS‐PSM meets the safety and electromagnetic compatibility (EMC) requirements listed in Table A‐4: Table A-4 Compliance Standards Item Standard Safety
Compliance Standards A-4 Specifications