Cut Sheet

To learn more about Enphase offerings, visit enphase.com
© 2016 Enphase Energy. All rights reserved. All trademarks or brands used are the property of Enphase Energy, Inc.
2016-06-02
INPUT DATA (DC) MODELS:
M250-60-2LL-S22,
M250-60-2LL-S25
MODELS:
M250-72-2LL-S22,
M250-72-2LL-S25
Commonly used module pairings
1
210 - 350+ W 210 - 350+ W
Compatibility 60-cell PV modules 60-cell and 72-cell PV modules
Maximum input DC voltage 48 V
62 V
Peak power tracking voltage 27 V - 39 V 27 V - 48 V
Operating range 16 V - 48 V 16 V - 60V
Min/Max start voltage 22 V / 48 V 22 V / 48 V
Max DC short circuit current 15 A 15 A
OUTPUT DATA (AC)
Peak output power 250 W
Maximum continuous output power 240 W
Nominal output current 1.15 A @ 208 VAC
1.0 A @ 240 VAC
Nominal voltage/range 208 V / 183-229 V @ 208 VAC
240 V / 211-264 V @ 240 VAC
Nominal frequency/range 60.0 / 57-61 Hz
Extended frequency range
2
57-62.5 Hz
Power factor >0.95
Maximum units per 20 A branch circuit 24 (three-phase 208 VAC)
16 (single phase 240 VAC)
Maximum output fault current 850 mA rms for 6 cycles
EFFICIENCY
CEC weighted efciency 96.5%
Peak inverter efciency 96.5%
Static MPPT efciency (weighted, reference EN50530) 99.4%
Night time power consumption 65 mW max
MECHANICAL DATA
Ambient temperature range -40ºC to +65ºC
Dimensions (WxHxD) 171 mm x 173 mm x 30 mm (without mounting bracket)
Weight 1.6 kg (3.4 lbs)
Cooling Natural convection - No fans
Enclosure environmental rating Outdoor - NEMA 6
Connector type MC4: M250-60-2LL-S22 and M250-72-2LL-S22
Amphenol H4: M250-60-2LL-S25 and M250-72-2LL-S25
FEATURES
Communication Power line
Integrated ground The DC circuit meets the requirements for ungrounded PV arrays in
NEC 690.35. Equipment ground is provided in the Engage Cable. No additional
GEC or ground is required. Ground fault protection (GFP) is integrated into the
microinverter.
Monitoring Enlighten Manager and MyEnlighten monitoring options
Transformer design High frequency transformers, galvanically isolated
Compliance UL 2703 recognized, UL1741/IEEE1547, FCC Part 15 Class B,
CAN/CSA-C22.2 NO. 0-M91, 0.4-04, and 107.1-01
1. No enforced DC/AC ratio. See the compatibility calculator at enphase.com/en-us/support/module-compatibility.
2. Frequency ranges can be extended beyond nominal if required by the utility.
Enphase
M250 Microinverter