IQ Load Controller Additional Info

Load and Solar Circuit Control using IQ System Controller Auxiliary Contacts
33 © 2021 Enphase Energy Inc. All rights reserved. December 16, 2021
Appendix B: Controlling air conditioning unit using a thermostat.
Auxiliary contact can be wired to intercept the control wire of a thermostat to an air conditioner
Figure 31: Using auxiliary contact for controlling air conditioning unit
Normally the air conditioning units are controlled by the thermostat. The air conditioner starts when it
receives a signal from a thermostat. The signal from the thermostat usually goes into an air handler unit
(typically indoors). The air handler unit in turn signals the condenser unit which is outdoors.
An auxiliary contact can be used to intercept the “cool” wire from the thermostat to the air handler. The
“cool” wire may also be called a “cool call” wire. Once this is done the IQ System Controller auxiliary
contacts need to be configured to shed loads automatically in off-grid as outlined in sections above.
When this is done:
When the system is on-grid the auxiliary contact stays closed. This ensures that the thermostat’s
signal goes to the air handler thereby ensuring the air handler and condenser operate as normal.
When the system goes off-grid, the auxiliary contact opens, interrupting the control signal from
thermostat to the air handling unit. Depending on the state of the condenser during the grid
transition the following can happen:
o If the condenser was running during grid transition, it will run for a cool down period,
typically a few minutes. The IQ Batteries must be sized appropriately to support the
steady state current requirement of the condenser, to ensure there is no microgrid
collapse during the cooldown period.
o If the condenser was not running during the grid transition, it will not start again during the
off-grid mode.
If the condenser is signaled to start at the same instant as the grid transition happens, the
condenser may try to start. The surge current may collapse the microgrid unless the system has
been designed to support the surge current. This is a very rare scenario, and the system recovers
within a few seconds to form the microgrid again. Since the thermostat has been disconnected
during the initial microgrid transition, the condenser will not start again in off-grid mode.
Note: IQ Battery must be sized appropriately to handle the power requirements of the external
compressor.
Note: Use Normally Closed Auxiliary contact to wire the thermostat as the contact opens when the grid
power goes off by default.