IQ Load Controller Additional Info

Load and Solar Circuit Control using IQ System Controller Auxiliary Contacts
2 © 2021 Enphase Energy Inc. All rights reserved. December 16, 2021
Overview
This document provides installers and design engineers with the information required to plan and configure
Smart Control (load and solar circuit control) using IQ System Controller Auxiliary contacts.
The Enphase Energy System (EES) must have sufficient power capability to sink all the power from the PV
system during transitions to off-grid and must source power to support all loads in intentionally islanded
(standalone) operation. This may not always be feasible. In such situations, auxiliary contacts in IQ System
Controller can be used to disconnect(shed) excess solar or heavy loads.
In addition, low priority loads with high power requirements may deplete energy storage. Auxiliary contacts
can be used to shed these large loads to help maintain energy in the storage system.
What are auxiliary contacts and how do they work?
The IQ System Controller has 5 relays rated for pilot duty at up to 24Vac/Vdc and 1A continuous current.
One is dedicated for generator function while the others are available for general use. The
contacts/terminals of the pilot relays are not energized by IQ System Controller i.e., they have no voltage
on them and are “dry”. When these contacts are connected to a voltage source, they are “wetted”. In this
document, we will be referring to these as auxiliary relays or contacts. The configuration of the relays is as
follows:
1. Two Normally Open (NO)
2. Two Normally Closed (NC), and
3. One NO relay used for starting a generator (optional)
While the auxiliary contacts have NO and NC electrical configurations, the Enphase Installer App
overrides this behavior when configuring the contacts. Once configured the contacts are closed when
on-grid and open when off-grid. In special load control modes, the contacts may be closed when off-grid if
battery charge exceeds a threshold or if a generator is running. Due to this IQ System Controller can
only be used with NO-type external definite purpose contactors or power relays to implement load
control or solar circuit control as described in this tech brief.
Note: Refer to the Generator support tech brief for documentation related to generator integration. This
tech brief covers load and solar circuit shedding using auxiliary contacts.
Auxiliary contact labelling in IQ System Controller
The figure below illustrates the auxiliary contacts at the bottom of the IQ System Controller smart switch.
It also shows the AC combiner, Generator and IQ Battery lugs.
Figure 1 Auxiliary contact labelling and usage