Technical data
Table Of Contents
- Important Information
- The Enphase Envoy Communications Gateway
- Installation Planning and Preparation
- Install the Envoy
- 1. Find the Envoy Serial Number
- /2. Register the Envoy
- 3. Find a Location for the Envoy
- 4. Connect to the Internet
- 5. Check the Internet Connection
- 6. Install the Modules and Microinverters
- 7. Check the Envoy’s Progress
- 8. Wall Mount the Envoy (Optional)
- 9. Build the Virtual Array
- 10. View System Performance in Enlighten
- Envoy Operation
- Troubleshooting
- Power Line Communication Troubleshooting
- Network Basics and Troubleshooting
- Issue: IP Address Problems
- Issue: LCD Screen Displays “-Web”
- Issue: LCD Screen Displays “Envoy Failure +Web or -Web”
- Issue: LCD Screen Displays "Scanning Inhibited"
- Issue: The Envoy has Good Signal Strength but is Too Far from the Router
- Issue: Wireless Adapter Wi-Fi Problems
- Issue: How Set Up Wi-Fi Without Wi-Fi WPS
- Issue: Internet Traffic is Slower After Installing a Bridge
- DHCP versus Static IP Addressing
- MAC Filtering
- Firewall Settings
- Replacing an Envoy
- Envoy Local Interface
- Technical Data
Envoy Installation and Operation
2014 Enphase Energy Inc. 141-00011 Rev 05
48
Clear GFI Tripped Condition
This condition occurs only with the M190, D380, M210, M200, M175 and some M215 microinverters. A solid
red status LED on the microinverter indicates a ground fault (GFDI) error. The LED will remain red and the
fault will continue to be reported by the Envoy until the error has been cleared.
If a microinverter registers a GFI Tripped condition, you can attempt to clear this condition through the Envoy
Interface. An Envoy is required to send the clear-gfi message to clear the condition. If the condition does not
clear after you perform the following procedure, contact Enphase Energy customer support at
support@enphaseenergy.com.
To send the clear-gfi message to a microinverter:
1. From the Administration menu, choose Device Conditions and Controls.
NOTE: Do not click or select the box under the column labeled Select.
2. Click on the serial number of the unit showing the GFI condition.
The Control Flags screen appears.
CAUTION: The other control flags (reboot and cmd-alert) on this screen should be used only
when recommended by Enphase. Their functions are:
reboot - reboots the inverter
cmd-alert - clears a condition flag for a command sent