Technical data
Envoy Installation and Operation
Copyright 2012 Enphase Energy 141-00014 Rev 03
36
Change or View the Grid Profile
Many Enphase Microinverters have field adjustable voltage and frequency trip points. Trip points are input
voltage or frequency values that trigger the microinverters to shut down when the values are exceeded. If
local regulations require adjustments to these trip points, the installer can set up the system to use an
alternate Grid Profile (set of trip points).
NOTE: Only an authorised installer, following the requirements of the local regulatory
authority, is allowed to make Grid Profile adjustments.
NOTE: Grid profile changes are applied only after a microinverter is detected.
In some regions and in some situations, microinverter trip points must be adjusted to account for high grid
voltage or for local conditions. Grid profile management tasks include:
Adjust system trip points for frequency and voltage if required by local utilities
Reset trip points to default values
View or verify current grid profile
Generate a report for confirmation of site settings to the utility or other authority
To change a grid profile, you need a “Change Token”. Change tokens are issued on a per Envoy serial
number basis. Contact Enphase Customer Support for your Grid Profile Change Token as directed on
the screen.
1. From the System Overview screen, click on Inventory and verify that all installed
microinverters are detected.
2. Click Administration to access the Administration menu.
The default log in credentials for the Administration menu are:
Username: admin
Password: admin
The System Administration screen appears.
Click to select Device
Grid Configuration