Technical data
Envoy Installation and Operation
Copyright 2012 Enphase Energy 141-00011 Rev 03
34
Clear GFI Tripped Condition
A solid red status LED on the microinverter indicates the microinverter has detected a ground fault
(GFDI) error. The LED will remain red and the fault will continue to be reported by the Envoy until
the error has been cleared.
If a microinverter registers a GFI Tripped condition, you can attempt to clear this condition through
the Envoy Interface. If the condition does not clear after you perform the following procedure,
contact Enphase Energy customer support at support@enphaseenergy.com.
To send the Clear-GFI message to a microinverter:
1. From the Admin menu, choose Device Conditions and Controls.
2. Click on the serial number of the unit showing the GFI condition.
NOTE: Do not click or select the box under the column labeled Select.
The Control Flags screen appears.
CAUTION: The other control flags (reboot and cmd-alert) on this screen should be
used only when recommended by Enphase. Their functions are:
• reboot - reboots the inverter
• cmd-alert - clears a condition flag for a command sent