10. Enter the authorization number from the Envoy Interface.
11. Click Get Token.
12. Copy the token.
13. Paste or enter the token in the Grid Profile screen.
14. Click Apply Grid Profile. This step propagates the settings to the microinverters.
Available profiles include:
IEEE 1547 Standard: The appropriate default for the majority of installations
IEEE 1547 Hawaii alternate: Used only to satisfy HELCO and MECO Utility
requirements and takes the AC frequency trip point down to 57.0Hz
IEEE 1547 High Line ACV: Relaxes the high line AC voltage trip point slightly
beyond the default while remaining within specification
The Apply Profile screen appears. This screen allows you to generate a report to
confirm that the microinverters have been set with an updated grid profile.