Technical data

Envoy Installation and Operation
Copyright 2012 Enphase Energy 141-00011 Rev 03
25
Is the system energized? PV modules power microinverters, PV modules provide power
only during daylight hours, and microinverters communicate only when powered.
Run another scan during daylight hours.
Check that the circuit breaker(s) for the PV array are in the “ON” position. For the Envoy
to communicate with the microinverters, the PV circuit breakers must be in the “ON”
position in the electrical load-center.
Verify that the PV modules are connected to the microinverters.
Envoy plugged into a circuit on the primary load-center, but the PV circuit breakers are on
a downstream sub-panel: The primary load-center is full and doesn’t have additional
capacity to add circuit breakers.
Add a subpanel with a small subset of circuit breakers. In this case, it is best to add an
additional 5-Amp circuit breaker and then run an outlet off that subpanel. Plug the
Envoy into that outlet, so that it can be close to the PV circuit breaker.
Local Area Networking Troubleshooting
PROBLEM: IP address issues. If the IP address displayed on the Envoy’s LCD screen is
169.254.120.1, or if the IP address does not match the DHCP subnet on the internal network, this
means that the Envoy was unsuccessful in obtaining a DHCP lease from the router.
Check network connectivity to the router or other DHCP server. You may also wish to
contact your Internet Service Provider or refer to your router documentation for
assistance.
Check that you are using a broadband router and not a switch or a hub. Many hubs
and switches cannot provide a DHCP lease and may not allow the Envoy to connect to
the web.
Use the Envoy menu button to “Get New IP Address”.
Unplug all units in the chain, applying power again in this order: Modem, Router, and
Envoy. Allow a few minutes for the IP address to be reassigned.
PROBLEM: LCD screen displays “-Web”. This means that the Envoy has no connection to the
Enlighten website.
Check network connectivity to the router. You may also wish to contact your Internet
Service Provider or refer to your router documentation for assistance.
Allow a few minutes longer. If the Envoy has recently received a valid IP address, it will
likely display +Web momentarily.
PROBLEM: LCD screen displays “Envoy Failure +Web or -Web”. This message displays after the
Envoy has tried unsuccessfully three times to initialize.
Unplug the Envoy from the electrical outlet and plug it in once again. Leave it in place
for at least 15 minutes. If it continues to display Envoy Failure or if it never moves
beyond the Initialization stage, call Enphase Customer Support.
PROBLEM: The Envoy is in a location that yields a good signal-strength, but using an Ethernet
cable here is not practical:
In this case, you may need to use power line communication bridges or a wireless
Ethernet bridge.