Troubleshooting
The following sections describe possible problems and solutions. For information on system status
and event messages, see “Event Messages” on page 38.
For more extensive Troubleshooting information, refer to the manual, Troubleshooting an Enphase
Installation at
http://www.enphaseenergy.com/support/downloads.
Power Line Communication Troubleshooting
At power-up, the Envoy performs a “Communication
Check”. After a few minutes, it will display a number
of bars in the LCD screen. This value, from 0 to 5,
indicates the signal strength of the power line
communication between the Envoy and the
microinverters. A number from 3-5 is good. A number
of 1-2 is not ideal. Zero bars means that either the Envoy needs to be relocated, or there are one or
more electrical appliances causing interference. Troubleshoot power line communication issues as
follows.
PROBLEM: The microinverter count doesn’t match number of installed units. This may indicate that
the Envoy is not done scanning/discovering the entire array. Alternatively, it may indicate that the
Envoy is having difficulty communicating over the power lines. It could also be a result of low light
levels and the PV module voltage being too low for the microinverter to power up.
• Make sure that the Envoy is plugged directly into the wall and not into a power strip or
surge protector.
• Relocate your Envoy as close to the electrical service-panel (load-center) as possible. This
ensures that the Envoy receives the strongest possible signal from each microinverter.
• Try unplugging any other device that may be sharing the outlet with the Envoy. Or, as
an alternative, plug the Envoy into a circuit that supports fewer electronic appliances.
Appliances sharing a receptacle with the Envoy may interfere with power line
communication.
• If this problem occurs when light levels are low, try again during daylight hours.
PROBLEM: Envoy displays fewer than three bars. Follow the previous procedure.
PROBLEM: Envoy displays zero bars. The following conditions may exist.
Is there a phase-imbalance?
• Ask the electrician to measure the conductors and neutral line to verify that the phases
are balanced. In cases where the phases are not balanced, electricians must recheck
their work.