User Manual

Planning for a Three-Phase IQ Microinverter System – North America
© 2017 Enphase Energy Inc. All rights reserved. September 20, 2017
7
Ampacity Calculations for Three-Phase Feeders to 208Y/120V Solar Subpanel
Calculate the ampacity of the three-phase, 208Y/120V solar subpanel feeders from the continuous output
power rating as follows:
# of Microinverters ∗ Inverter Continuous Output Power Rating = Total Continuous Output Power
Total Continuous Output Power / 208𝑉 / 1.732 = Solar Subpanel Continuous Ampacity
IQ 6 (208V)
IQ 6+ (208V)
Continuous Output Power Rating
230VA
280VA
For a solar subpanel with 231 IQ 6+ Microinverters, the continuous output current rating is:
231280𝑉𝐴 = 64,680𝑉𝐴
64,680𝑉𝐴 / 208𝑉 / 1.732 = 179.54𝐴
NEC Article 690.9(B) requires a 125% factor be applied to the continuous output current for sizing
overcurrent protection of the branch circuit:
179.54𝐴 ∗ 1.25 safety factor = 224.4𝐴
A 225A overcurrent protection device (OCPD) is required for 231 - IQ 6+ Microinverters at 208Y/120V.
208Y/120V Electrical Schematic