branch circuit breaker wired directly off the solar subpanel. Wire the IQ Envoy with two hot conductors and a
neutral.
A 208Y/120V interconnection is a Wye type interconnection. A Wye utility service requires a neutral ground
bond at the center point of the transformer.
208Y/120V Electrical Service Conceptual Schematic
Ampacity Calculations for 208V Branch Circuits on Two-Pole Circuit Breakers
Calculate the ampacity of a two-pole branch circuit as follows:
# ππ ππππππππ£πππ‘πππ β πΌππ£πππ‘ππ πΆπππ‘ππππ’π ππ’π‘ππ’π‘ πΆπ’πππππ‘ π
ππ‘πππ = π΅ππππβ πΆππππ’ππ‘ ππ’π‘ππ’π‘ πΆπ’πππππ‘
IQ 6 (208V)
IQ 6+ (208V)
Continuous Output Current Rating
1.11A
1.35A
For a fully populated branch circuit of 11 IQ 6+ Microinverters, the continuous output current rating is:
11 β 1.35π΄ = 14.85π΄
NEC Article 690.9(B) requires a 125% factor be applied to the continuous output current for sizing
overcurrent protection of the branch circuit:
14.85π΄ β 1.25 safety factor = 18.6π΄
A 20A branch circuit overcurrent protection device (OCPD) is required for 11 IQ 6+ Microinverters at 208V.