User Manual
Planning for a Three-Phase IQ Microinverter System – North America
© 2017 Enphase Energy Inc. All rights reserved. September 20, 2017
19
Q Commercial Relay Controller (Q-RELAY-3P-NA) for Dropped Phase
and Neutral Protection
The Enphase Q Commercial Relay Q-RELAY-3P-NA monitors
line and neutral voltages and signals the coil of a contactor in
case of a dropped phase or opened neutral. The relay
controller is field selectable with support for 120/208Y and for
240V high-leg delta applications.
The Q Commercial Relay is not required for the IQ
microinverter to function, but may be required by some AHJs
and/or utilities.
You must use a “normally opened” contactor sized for the
power rating of the PV system. A 120V coil is shown in the
following schematic. For this example, a 350A continuous
rated contactor with 400A max circuit breaker rating is shown.
The contactor was sized based upon the kW rating.
Contactor shown for 65kW, 208V system:
ABB Contactor AF260-30-11-12
Sample Schematic of 208Y/120V System with Q
Commercial Relay