Interconnecting IQ Microinverters to Other Voltages
For interconnection to system voltages other than 120/240V single-phase, 120/208 single-phase, 208Y/120V
three-phase, and 240V high-leg delta three-phase, a transformer is required to interconnect to the grid.
While transformers interconnect Enphase Microinverter Systems to any utility power voltage, they also offer
other benefits.
For many projects, it is cost effective to distribute the power at the higher utility voltages and then
step down the voltage to 208Y/120V or 240V high-leg delta at each sub-system. This practice results
in more transformers, but can be cost effective when wire runs are greater than 250 feet.
Choose transformers with adjustable taps. Use the tap to make minor adjustments when the utility-
provided voltage is high or when optimizing conductor sizing versus expected voltage rise for the
value engineered PV system.
It is common to specify high-efficiency or ultra-high efficiency,
general purpose, dry-type transformers for an Enphase
Microinverter System. It is not necessary to specify power factor
correcting transformers or K-factor transformers.
Specify the transformer kVA size to meet the inverter output in kW
AC. Some additional deratings, such as adjustments for power
factor and temperature may apply. Refer to the transformer
manufacturer’s specifications for transformer sizing.
Most transformers for Enphase systems are specified as delta on
the primary/utility side and as 208/120 Wye or 240V high-leg delta
on the secondary/PV side. Even if the utility voltage is Wye, such
as a 480Y/277V service, it is still best to provide a delta
configuration with no neutral to the primary/utility side of the
transformer. This configuration works well, lowers wire costs, and
is recommended by the manufacturers of transformers for
improved performance and reduced harmonics.
Delta and Wye Wiring
The following table lists utility voltage values and transformer requirements.