Install Manual

Enphase Customer Support: enphase.com/en-us/support/contact
Safety and Advisory Symbols
+
DANGER: This indicates a hazardous situation, which if not avoided, will result in
death or serious injury.
*
WARNING: This indicates a situation where failure to follow instructions may be a
safety hazard or cause equipment malfunction. Use extreme caution and follow
instructions carefully.
NOTE: This indicates information particularly important for optimal system opera-
tion. Follow instructions carefully.
Safety Instructions
+
DANGER: Risk of electric shock. Risk of re. Only qualied electricians should install,
troubleshoot, or replace the IQ
TM
Battery(ies).
+
DANGER: Risk of re or explosion. Only qualied personnel, using personal protective
equipment (PPE) should transport or handle the IQ
TM
Battery(ies).
+
DANGER: Risk of explosion. Do not dispose of IQ
TM
Battery(ies) in a re or by burn-
ing. The IQ
TM
Battery(ies) can explode.
+
DANGER: Risk of re or explosion. This product is designed for stationary installa-
tion only and should be used accordingly. It is not designed for mobile applications
such as installation and on vehicles and trailers and should not be used in such
applications.
+
DANGER: Risk of re. During use, when stored, or during transport, keep the IQ
TM
Battery(ies) in an area that is well ventilated and protected from the elements,
where the ambient temperature and humidity are within -15° C to 55° C (5° F to
131° F) and 5% to 100% RH, non-condensing, preferably out of direct sunlight. Do
not install the IQ
TM
Battery(ies) at elevations over 2500 m (8,200 feet) above sea
level.
+
DANGER: Risk of re. If the IQ
TM
Battery(ies) generate smoke, remove AC power
from the Enphase System and turn the DC connect switch to the off position so
that charging/discharging stops.
+
DANGER: Risk of electric shock. Risk of re. Do not attempt to repair the IQ
TM
Bat-
tery(ies). DO NOT OPEN THE ENCLOSURE -- NO SERVICEABLE PARTS. Tampering
with or opening the IQ
TM
Battery(ies) will void the warranty. If the IQ
TM
Battery(ies)
fail, contact Enphase Customer Support for assistance at enphase.com/en-us/
support/contact.
+
DANGER: Risk of electric shock. Do not use Enphase equipment in a manner not
specied by the manufacturer. Doing so may cause death or injury to persons, or
damage to equipment.
+
DANGER: Risk of electric shock. Do not install the IQ
TM
Battery(ies) without rst
removing AC power from the photovoltaic system. Disconnect the power coming
from the photovoltaics before servicing or installing.
+
DANGER: Risk of electric shock. Always de-energize the AC branch circuit during an
emergency and/or before servicing the IQ
TM
Battery(ies). Never disconnect the DC
switch under load.
+
DANGER: Risk of electric shock. Risk of high short-circuit current. Observe the
following precautions when working on batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear insulating gloves and boots.
Do not lay tools or metal parts on top of batteries.
+
DANGER: Risk of electric shock. Risk of re. Do not work alone. Someone should be
in the range of your voice or close enough to come to your aid when you work with
or near electrical equipment.
+
DANGER: Risk of re. Do not allow or place ammable, sparking, or explosive items
near the IQ
TM
Battery(ies).
+
DANGER: Risk of electric shock. In areas where ooding is possible, install the IQ
TM
Battery(ies) at a height that prevents water ingress.
+
DANGER: Risk of electric shock. AC voltage is present at the output when the DC
switch is on.
+
DANGER: Risk of electric shock. Branch circuit protection must be off before
switching DC power on or off.
+
DANGER: Risk of electric shock. The DC switch must locked in the OFF position for
shipping and service.
*
WARNING: Risks of electric shock, energy hazard, and chemical hazard. Do not
disassemble.
*
WARNING: Risk of equipment damage. During use, storage, transport, or installa-
tion, always keep the IQ
TM
Battery(ies) in an upright position.
*
WARNING: You must install the IQ
TM
Battery(ies) only on a suitable wall using an
Enphase wall-mount bracket.
*
WARNING: Before installing or using the IQ
TM
Battery(ies), read all instructions and
cautionary markings in this guide and on the equipment.
*
WARNING: Do not install or use the IQ
TM
Battery(ies) if it has been damaged in any
way.
*
WARNING: Do not exceed the maximum number (3) of IQ
TM
Batteries in a 20 A AC
branch circuit.
*
WARNING: Do not sit on, step on, place objects on, or insert objects into the IQ
TM
Battery(ies).
*
WARNING: Do not place beverages or liquid containers on top of the IQ
TM
Battery(ies).
Do not expose the IQ
TM
Battery(ies) to liquids or ooding.
*
WARNING: When placing the IQ
TM
Battery(ies) in storage, ensure that AC power
is not present and that the DC switch is in the Locked position. While in storage,
damage to the battery can occur from over-discharge. If the battery state of charge
falls to 0%, the IQ
TM
Battery(ies) can be damaged or destroyed. Because of this, the
IQ
TM
Battery(ies) must only be stored for a limited amount of time.
• The
IQ
TM
Battery
(ies) must be installed and energized by the “Must
Energize By” date on the shipping box label.
• The
IQ
TM
Battery
(ies) must have a charge state of no more than 30%
when placed in storage. To do this, the
IQ
TM
Battery
(ies) must be placed
in Sleep Mode.
• If the
IQ
TM
Battery
(ies) is already been installed, it must be placed
into Sleep Mode prior to uninstalling. A battery in Sleep Mode can be
stored a maximum of two months after being placed into Sleep Mode.
NOTE: Perform installation and wiring, including protection against lightning and
resulting voltage surge, in accordance with all applicable local electrical codes and
standards.
NOTE: Because IQ
TM
Battery(ies) are grid forming, you must install signage in
accordance with NEC articles 705, 706, and 710.
NOTE: Using unapproved attachments or accessories could result in damage or
injury.
NOTE: Install properly rated over current protection as part of the system installa-
tion.
NOTE: To ensure optimal reliability and to meet warranty requirements, the IQ
TM
Battery(ies) must be installed and/or stored according to the instructions in this
guide.
NOTE: The IQ
TM
Battery(ies) are compatible only with the IQ
TM
Gateway commu-
nications gateway properly tted with USB hub, USB radios, and production
and consumption CTs. The IQ
TM
Gateway is required for operation of the IQ
TM
Battery(ies). Earlier versions of the Enphase Gateway communications gateway are
incompatible.
NOTE: The Enphase IQ
TM
Battery(ies) are intended to operate with an Internet con-
nection. Failure to maintain an Internet connection may have an impact on the war-
ranty. See Limited Warranty for full terms and services (enphase.com/warranty).
NOTE: When replacing Enphase IQ
TM
Battery(ies), you must replace with an IQ
TM
Battery(ies) of the same type, with the same AC current rating.
NOTE: When disconnected and stored, no automatic charge of the battery is
possible.
NOTE: Properly mount the IQ
TM
Battery(ies). Ensure that the mounting location is
structurally suited to bearing the weight of the IQ
TM
Battery(ies).
NOTE: During use, storage, and transport, keep the IQ Battery(ies):
Properly ventilated
Away from water, other liquids, heat, sparks, and direct sunlight
Away from excessive dust, corrosive and explosive gases, and oil smoke
Away from direct exposure to gas exhaust, such as from motor vehicles
Free of vibrations
Away from falling or moving objects, including motor vehicles. If mounted
in the path of a motor vehicle, we recommend a 91 cm (36-inch)
minimum mounting height
At an elevation of lower than 2,500m (8,200 feet) above sea-level
In a location compliant with re safety regulations
In a location compliant with local building codes and standards
NOTE: Conditions for the IQ Battery installation site apply also to storage condi-
tions.
SAFETY
IMPORTANT SAFETY INSTRUCTIONS. SAVE THESE INSTRUCTIONS. This guide contains important instructions that you must follow during installation
and maintenance of the Enphase IQ
TM
Battery(ies). Failing to follow any of these instructions may void the warranty (enphase.com/warranty).
In Case of Fire or Other Emergency
In all cases:
If safe to do so, switch off the AC breaker for the IQ
TM
Battery circuit, and if
an isolator switch is present, switch off the AC isolator for the IQ
TM
Battery
circuit.
Contact the re department or other required emergency response team.
Evacuate the area.
In case of re:
When safe, use a re extinguisher. Suitable types are A, B, and C dry chemical
re extinguishers. Additional extinguishing media include carbon dioxide, or
alcohol-resistant foams.
In case of ooding:
Stay out of the water if any part of the IQ
TM
Battery(ies) or wiring is
submerged.
If possible, protect the system by nding and stopping the source of the
water, and pumping it away.
If water has contacted the battery, call your installer to arrange a inspection.
If you are sure that water has never contacted the battery, let the area dry
completely before use.
In case of unusual noise, smell or smoke:
Ensure nothing is in contact with the IQ
TM
Battery(ies) or in the venting area
of the IQ
TM
Battery(ies).
Ventilate the room.
Contact Enphase Customer Support at enphase.com/en-us/support/contact.
Safety Instructions, continued
Environmental Protection
ELECTRONIC DEVICE: DO NOT THROW AWAY. Waste electrical
products should not be disposed of with household waste.
Proper disposal of batteries is required. Refer to your local
codes for disposal requirements.