14
Provide Power for the Envoy-S Metered (ENV-S-AM1-120)
The Envoy-S Metered (ENV-S-AM1-120) does not include an AC power cord, and you must hard-wire it.
When you hard-wire the Envoy-S, you must install it in a ventilated, non-metallic, NRTL certified NEMA type
3R-rated (or better) enclosure with conduit attachment.
DANGER! Risk of electric shock. Be aware that installation of this equipment includes risk of
electric shock. If you wire the Envoy-S at the subpanel, always de-energize the subpanel before
beginning wiring.
a. Use a 15 A maximum circuit breaker for the supply wiring.
b. Make sure supply wiring is 14 AWG rated at 75 degrees C or better.
c. Locate the screw on the left side of the terminal block door, and loosen it with a screwdriver to unlock
the door.
d. Flip open the terminal block door and wire the line and neutral conductors as shown in the diagram.
Tighten terminal block screws to 5 in-lbs.
- Connect Line 1 to A
- Connect Line 2 to B
- Connect Neutral to N