IQ System Controller 2 Quick Install Guide
AWG TORQUE (LB.IN)
300kcmil-2 250
AWG TORQUE (LB.IN)
300kcmil-2 275
AWG TORQUE (LB.IN)
Neutral and Ground
bar – large holes
1/0 - 3 50
4 - 6 45
8 40
10 - 14 35
Neutral and Ground
bar – small holes
6 - 8 25
10 - 14 15
Larger neutral bar 300kcmil - 6 275
Mains/ Supply side wiring
The mains wiring is to be the nal step in the installation process.
The wiring is similair for both full home and partial home back up.
300 kcmil-2 AWG
1/4’’
1/4’’
300 kcmil-1/0 AWG
300kcmil to 14 AWG
3/8’’
3/8’’
300 kcmil to 14 AWG
Section C - Wiring