Technical Brief for Installation of Consumption Monitoring

Installing Consumption CTs
2016 Enphase Energy Inc. All rights reserved. January 2016
5
Location of the Envoy-S Metered
To simplify the wiring of the consumption CTs, locate the AC
Combiner Box and/or Envoy-S Metered at or near the main
service panel.
If you are installing the Enphase AC Combiner Box, the
Envoy-S Metered comes with the production CT and the
Envoy-S prewired for power.
Installation of Consumption CTs
For consumption monitoring to work correctly, you must meet
the following installation requirements:
Attach the consumption CT installed on terminal IA
(line 1) to the same line as power terminal A of the
Envoy-S. Verify with a voltmeter.
Make sure that the arrow on the consumption CT faces toward the loads.
Wire the consumption CTs with the white wire installed on the upper row of wiring terminals and the
blue wire installed on the lower row of wiring terminals.
Do not use the Envoy-S terminal block on the right side.
NOTE: You must install the CT wired to terminal IA on the same line as the Envoy-S power terminal A.
Installing CTs in a simple scenario
When the conductors or busbars between the main service meter and service panel are accessible,
complete the wiring as shown above as described in the
Enphase Envoy-S Installation and Operation Manual.