Envoy S Installation
Table Of Contents
- SAFETY
- The Enphase Envoy-S
- Installation Planning and Preparation
- Installing the Envoy-S
- Activate Monitoring
- Envoy-S Operation
- Connecting to Envoy-S
- Troubleshooting
- Technical Data
Envoy-S Installation and Operation
2015 Enphase Energy Inc. 141-00027 Rev 01
51
Internet Connection Options
Integrated Wi-Fi
802.11b/g/n
Ethernet
802.3, Cat5 Ethernet cable (not included)
Cellular
Optional, CELLMODEM-01 (not included)
Measurement Circuit
Voltage
120 VAC or 120/240 VAC or 208Y/120 VAC at the power input terminal block
Current
Up to 200 A via CT inputs
Measurement Circuit
Per IEC/EN/CSA/UL 61010, CAT III
Metering options
Model ENV-S-AM1-120: Revenue grade production and consumption
metering; ANSI C12.20, 0.5 accuracy class (pending).
Model ENV-S-AB-120-A: Standard reporting; Accuracy +/- 5.0%
CSI Eligibility
The Envoy-S is included in the List of Eligible System Performance Meters for the
CSI program (pending).
Compliance
Compliance
UL 916,
CAN/CSA C22.2 No. 61010-1,
CAN ICES-003 (B)/NMB-003(B),
47 CFR, Part 15, Class B,
IEC/EN 61010-1:2010,
EN50065-1, EN61000-4-5, EN61000-6-1, and EN61000-6-2
Metering: ANSI C12.20 accuracy class 0.5 (ENV-S-AM1-120) (pending).