User's Manual

USER MANUAL
PTM 535 / PTM 535U / PTM 535J ENOCEAN TRANSMITTER MODULE
© 2019 EnOcean | www.enocean.com F-710-017, V1.0 PTM 535 / 535J User Manual | v1.5 | September 2020 | Page 12/33
3 Radio telegram format
3.1 Standard mode
In standard configuration, PTM 535 transmits the same telegram type as the PTM 210
pushbutton module. The telegram information is encoded within a 7 byte RPS telegram as
shown in Figure 4 below.
Figure 4 PTM 535 telegram format
This telegram format uses the following fields:
Telegram type (RORG, 1 byte)
The telegram type is always 0xF6 indicating an RPS telegram
Switch data (DATA, 1 byte)
This field encodes the buttons that have been pressed. The encoding depends on the
number of buttons that have been pressed.
EnOcean Unique Radio IO (EURID, 4 byte)
This field contains the ID which uniquely identifies each EnOcean products
Switch status (STATUS)
This field encodes certain properties of the telegram as shown in below.
The STATUS field identifies the message type (U-Message or N-Message) as well as the
repeater level (original telegram, 1 hop repeated, 2 hop repeated) as shown in Figure 5
below.
Figure 5 STATUS field encoding