User's Manual
USER MANUAL PREVIEW
PTM 535BZ – BLUETOOTH AND ZIGBEE GREEN POWER PUSHBUTTON TRANSMITTER
© 2022 EnOcean | www.enocean.com F-710-017, V1.0 PTM 535BZ User Manual | v1.2 | July 2021 | Page 38/121
The Generic Switch Configuration field which identifies the type of switch and the number of
supported switch contacts. It is by default set to 0x01 (unknown switch type, one switch
contact) as the majority of PTM 535BZ applications are single push buttons or position
switches. The number of contacts can be changed to other values via the NFC interface as
described in Chapter 5.6.11.
The Current Contact field identifies the input status when the commissioning telegram was
triggered allowing different receivers to identify and respond to different button actions.
Figure 31 below shows the encoding of the Current Contact field.
Figure 31 – Current Contact encoding
4.4.2.3 Application Information for Device ID other than 0x07
The Application Information structure for Device ID other than 0x07 contains the list of sup-
ported commands. Figure 32 below illustrates the Application Information structure for De-
vice ID other than 0x07.
Figure 32 – Application Information structure for Device ID other than ID 0x07
The Application Information Type field is set to 0x04 specifying that the CommandID List (list
of supported commands) follows.
The Application Information Length field contains the number of commands that follow.
If the default command set (eight commands as listed in Table 8) is used, then the Application
Information structure will have the content shown in Figure 33 below. If the commands in
Table 8 are configured to different CommandID by the user then the CommandID List will
change accordingly. If commands are set to non-active (0xFF) then these will be omitted
from the list which will be shortened accordingly.
Figure 33 – Application Information content with default command list