1.4 Environmental Conditions
Operating temperature -25 °C … +65 °C
Storage temperature -40 °C … +85 °C
Humidity 0% … 93% r.h., non-condensing
1.5 Ordering Information
Type
Ordering Code
Frequency
PTM 335
S3001-A335
868.3 MHz
PTM 335C
S3031-A335
315.0 MHz
2 FUNCTIONAL DESCRIPTION
2.1 Block diagram
At power-up by an energy pulse at AC1, AC2 a DC voltage is provided to the internal micro
controller. The microcontroller reads the polarity of the supply voltage pulse.
After that 3 identical radio telegrams containing polarity information and 32 bit module ID
are transmitted.
2.2 Pin out and pin description
Symbol
Function
Characteristics
AC1
Input for ECO 200
ECO 200 or
equivalent energy pulse
AC2
Input for ECO 200
ECO 200 or
equivalent energy pulse
RF_HELIX
RF output
Output for pre-installed
helical antenna