Installation
Caution
Installation and maintenance must be performed by a qualified
electrician in accordance with local, state, and national electrical
codes (NEC) and requirements.
LED Description
Step 1: De-energize the luminaire.
Step 2: Determine the location of the sensor. Push and
rotate the anchor screw to the tile at that location.
Step 3: Select a place near the anchor screw for the RJ12
connector of the sensor cable from the Control Unit (CU)
to exit. See Wiring Diagram on Page 4.
Make a small cut in the ceiling tile for the cable to exit.
Step 4: Connect the RJ12 connector to the sensor
bottom.
Step 5: Slide the Smart Sensor onto the screw head.
Step 6: Slip the excess sensor cable up into the plenum
area and adjust the ceiling tile to the original position.
Step 7: Energize the luminaire and confirm that the
green LED is solid.
Anchor Screw
Sensor Cable
The Smart Sensor (SU-5S) should be mounted to the ceiling
tile within a few inches (between 1
3/4
” to 3”) of the lighting
fixture.
For wiring connections from the Control Unit to the sensor,
refer to the Control Unit Installation Guide.
Wiring Diagram:
LED Status Description/Solution
LED not on Check power and wiring
Green blinking Sensor commissioned and working
Red blinking Sensor not commissioned
Red solid Faulty sensor replace sensor
Green solid Sensor installed, initialized, and uncommissioned
waiting for discovery.
Blue solid Sensor received a request to identify itself