User's Manual
Table Of Contents
Page 2 Page 3 Page 4
Installation
Caution
Installation and maintenance must be performed by a qualified
electrician in accordance with local, state, and national electrical
codes (NEC) and requirements.
LED Description
Step 1: De-energize the luminaire.
Step 2: Determine the location of the sensor. Push and
rotate the anchor screw to the tile at that location.
Step 3: Select a place near the anchor screw for the RJ12
connector of the sensor cable from the Control Unit (CU)
to exit. See Wiring Diagram on Page 4.
Make a small cut in the ceiling tile for the cable to exit.
Step 4: Connect the RJ12 connector to the sensor
bottom.
Step 5: Slide the Smart Sensor onto the screw head.
Step 6: Slip the excess sensor cable up into the plenum
area and adjust the ceiling tile to the original position.
Step 7: Energize the luminaire and confirm that the
green LED is solid.
Anchor Screw
Sensor Cable
The Smart Sensor (SU-5S) should be mounted to the ceiling
tile within a few inches (between 1
3/4
” to 3”) of the lighting
fixture.
For wiring connections from the Control Unit to the sensor,
refer to the Control Unit Installation Guide.
Wiring Diagram:
LED Status Description/Solution
LED not on Check power and wiring
Green blinking Sensor commissioned and working
Red blinking Sensor not commissioned
Red solid Faulty sensor – replace sensor
Green solid Sensor installed, initialized, and uncommissioned
– waiting for discovery.
Blue solid Sensor received a request to identify itself