Instruction Manual

Page 2 Page 3 Page 4
Installation
Figure 5
Caution
Installation and maintenance must be performed by a qualified
electrician in accordance with local, state, and national electrical
codes (NEC) and requirements.
Figure 1
LED Status Description/Solution
LED not on Check power and wiring
Purple solid All LEDs are on during boot time for 5-6
seconds
Green blinking Sensor commissioned and working
Red blinking Incompatibility between LED driver and sensor
Replace LED driver and if not resolved,
replace sensor.
Red solid Faulty sensor replace sensor
Green solid Sensor installed, initialized, and
uncommissioned waiting for discovery.
Blue solid Image being upgraded.
LED Description
Step 1: Turn off all power to the light fixture by switching off
the circuit breaker.
Step 2: Mount the Control Unit (CU) in a UL approved
enclosure. Refer to the Control Unit Installation Guide. See
Figure 5 for the wiring connections from the CU.
Step 3: Determine the
location of the sensor in
the fixture. Figure 1.
The Smart Sensor (SU-4S)
should be mounted to
the ceiling within a few
inches (between 1
3/4
” to
3”) of the lighting fixture
and over the service
area of the light.
Step 4: Select a place for
the RJ12 data cable
from the CU to exit and
make a small cut in the
ceiling tile for the cable
to exit.
Step 5: Install the Smart Sensor
anchor screw (as shown).
Figure 3.
Step 6: Connect the RJ12
data cable to the Sensor
(bottom entry). Figure 3.
Step 7: Slide the Smart Sensor onto the screw head.
Step 8: Slip the excess RJ12 data cable up into the plenum
area and adjust the ceiling tile to the original position.
Figure 4.
Step 9: Switch on the circuit breaker to turn the power on.
Figure 2
Figure 3
Figure 4
Anchor Screw
RJ12 Cable
1”
Drill 5/8”
hole