User manual

Code: ENIGMA III User Manual
Edition: 1 Revision: 4
Date: 19/12/2008
Page: 45/97
Example:
Configure sector blanking for a sector 10°-16° azimuth for elevation -5° to 3°.
set SectorblankingTable 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0
0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0
63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0
0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0
0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768
0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0
0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63 32768 0 0 0 0 0 0 0 0 0 0 63
32768 0 0 0 0 0 0 0 0 0 0
Remark: Please note that only the elevation tables from -5° to 3° have been given. ENIGMA
automatically fills the table with 0's at the end.
6.3.2 SectorblankingEnabled
Type: bool
Default: false
With the parameter SectorblankingEnabled sector blanking can be enabled/disabled. Upload the table
once and use this parameter to toggle sector blanking.
6.4 Serial TAGS
As an option the ENIGMA signal processor can read the angle TAGS from a serial (RS422) line instead
of the 16bit parallel TAG lines. The serial interface has several configuration options.
6.4.1 PCIRecTagBaudRate
Specify the baudrate for the RS422 TAG input at the ENIGMA host. The baudrate can be specified
directly in baud (1200...4000000) and can also be a “non-standard” value like 500000 (500kbits/s).
Type: integer
Default: 9600
Unit: baud
GAMIC Proprietary