Hardware Configuration Configuring an Analog Output
VisiLogic: Getting Started 51
Configuring an Analog Output
Analog I/O Ranges
Note that devices used in conjunction with the controller must be calibrated
according to the available range. Below, Range refers to the value contained
by the register that is linked to the I/O in Hardware Configuration.
Model number Resolution Range
V200-18-E1 (Snap-in I/O module)
V120-12-R1, V120-12-R2C
M90 controllers (analog input)
M91-19-R1, M91-19-R2, R2C
10 bit (0-10V, 0-
20mA,
4-20mA)
0-1023, 1024 units
(except at 4-20mA)
204 to 1024, 820 units (at
4-20mA)
V120-12-UN2
M90-19-UN2
M91-19-TC2
14 bit (0-10V, 4-
20mA)
Temperature
0-16383, 16384 units
(except at 4-20mA)
3277-16383, 13107 units
(at 4-20mA)