Specifications
Replacing or Removing the Battery Appendix B: Vision Controller Divisions
124 VisiLogic: Getting Started
Ladder
Feature
V120
V130
Call Subroutine
A single net can include
2
Call Subroutine functions
A single net can include
only 1
Call Subroutine function
Load HMI Display
A single net can include
2
Load HMI Display functions
A single net can include
only 1
Load HMI Display function
HMI
Feature
V120
V130
Load Subroutine
SB 33 Load Display with
linked Call Subroutine
turns ON for 1 scan
Each Display is linked to 3
subroutines:
The first runs when the
Display begins to load
The second runs while
the Display is shown
The third runs when the
Display begins to unload
Unload
Subroutine
SB 34 UnLoad Display
with linked Call
Subroutine turns ON for 1
scan
What is current
Display?
According to SI 252
Current HMI Display
Number
Use Ladder function HMI>HMI
Display Loaded (SI 252 not
relevant)
What was
Previous HMI
Display?
According to SI 251
Previous HMI Display
Number
Use
Ladder function HMI>Is
Last HMI Display Loaded (SI
252 not relevant)
Moving Images
Supported
Not supported. Are removed
when the project is converted
Variables
Day of
Week/Month
These variables occupy
less screen area in V120.
When converting an
application from V120 to
V130, you must manually
resize these variables
Hide/Invert
Variable
Use the Ladder elements
Invert/Hide Var
Use the Hide or Inverse /view
bit in the Variable's properties
Global Variables
Supported
Not supported; each Global
Variable is replaced with a
separate variable when the
project is converted
Keypad Entry
Variables
SB 92 Keypad Entry in
Progress (ON during
entry) (Enhanced
Vision)..
SB 93 Keypad Entry Var
Activates (ON for 1 scan)
(Enhanced Vision)..
SB 94 Keypad Entry Var
Complete (ON for 1 scan)
(Enhanced Vision)..
SB 250 HMI key entry
within limits (Standard
Vision only)
SB 251 Keypad entry
exceeds limits (Standard
SB 92 Keypad Entry in
Progress (ON during entry)
(Enhanced Vision)
SB 93 Keypad Entry Var
Activates (ON for 1 scan)
(Enhanced Vision)
SB 94 Keypad Entry Var
Complete (ON for 1 scan)