Specifications

Appendix A: Troubleshooting Compile
VisiLogic: Getting Started 109
Vision models
V120-12-R1, V120-12-R2C, V200-18-E1, V200-18-E1B and V200-18-
E2B
Analog value: from 0 to 1023 (10 bit). If the analog input is:
Below 0V/0mA, then the analog value will be 0.
Above 10V/20mA (about 2% above the full scale), then the analog value
will be 1024.
V120-12-UN2, V120-12-UA2
Analog value: from 0 to 16383 (14 bit). If the analog input is:
Slightly below 0V/0mA (about 0.5% below 0V/0mA), then the analog
value will be -1.
Slightly above 10V/20mA (about 0.5% above the full scale), then the
analog value will be 16384.
Greatly below or above of the analog input range, but still in the range of
the absolute maximum rating, then the analog value will be 32767.
Note that the absolute maximum rating of the analog inputs for all the units is
+/- 15V.
Compile
To test your project, compile it.
1. Select Compile from the Build menu.
2. After compiling the project, VisiLogic displays errors in the Output
Window.
Clicking the Compile tab displays the last compiled results.
Compilation Error Message #37
Message # 37 is displayed when a V120-12-xx is selected in the project's
Hardware Configuration, and the project contains a function that is not
supported by that model.