Installation Guide
9
IMPORTANT! READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING
THE UNIT AS SPECIFIED, AND REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED.
ENGLAND’S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT,
OR DUE TO UNSAFE INSTALLATION OR USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY
QUESTIONS.
INSTALLATION
AdditionalVentingInformation
x Donotmixandmatchcomponentsfromdifferentpipemanufacturerswhenassemblingyour
ventingsystem(i.e.DoNOTuseventingpipefromonemanufacturerandathimblefrom
another).
x Werequireaminimumverticalriseof36in.(3ft.)ofpipetocreatenaturaldraftinthesystem,
whichhelpsevacuatesmokefromthestoveintheeventofapowerfailureorcombustion
blowerfailure.
x Ventingsystems15.0ft.orshortermaybecomposedentirelyof3.0in.pelletpipe;toreduce
frictionallosses,ventingsystemslongerthan15.0ft.shouldbecomposedof4.0in.pelletpipe.
x Donotterminatetheventingsystemdirectlybeneathanycombustiblestructuresuchasa
porchordeck.
x FollowNFPA211ruleslistedbelowforventingsystemterminationlocationrelativetowindows
andotheropeningsinthedwelling.
o NFPA211(2006ed.)Section10.4Termination:10.4.5
(1)Theexitterminalofamechanicaldraftsystemotherthandirectventappliances
(sealedcombustionsystemappliances)shallbelocatedinaccordancewiththe
following:
(a)Notlessthan3ft.(.91m)aboveanyforcedairinletlocatedwithin10ft.
(3.0m).
(b)Notlessthan4ft.(1.2m)below,4ft.(1.2m)horizontallyfromor1ft.(305
mm)aboveanydoor,windoworgravityairinletintoanybuilding.
(c)Notlessthan2ft.(0.61m)fromanadjacentbuildingandnotlessthan7ft.
(2.1m)abovegradewhenlocatedadjacenttopublicwalkways.
x Distancebetweentheterminationopeningandgradeshouldbeaminimumof2ft.(24in.)
contingentonthegradesurfacebelowthetermination.Whendeterminingthetermination
heightabovegrade,considersnowdriftlinesandcombustiblessuchasgrassorleaf
accumulation.Inareaswheresignificantsnowfallispossible,theterminationheightmustbe
sufficientlyhightokeeptheterminationfreeofsnowaccumulation.
x Donotusemakeshiftcompromisesduringinstallationorinstallanycomponentoftheunitor
ventingsysteminsuchamannerthatcouldresultinahazardousinstallation.
x Achimneyconnector
shallnotpassthroughanatticorroofspace,closetorsimilarconcealed
space,orafloor,orceiling.
x Wherepassagethroughawallorpartitionofcombustiblematerialisdesired,theinstallation
shallconformtoCAN/CSAB365.
WARNING:
VentingsystemsurfacesgetHOT,andcancauseburnsiftouched.Noncombustibleshielding
orguardsmayberequired.