Specifications
72 Solution 2.5-ZC Fireplace Installation and Operation Manual   
The duct system must be installed respecting the following: 
1.  Remove the plates closing up the 8" dia. holes on top of the fireplace. Then, cut the 
insulation in order to obtain two 8" dia. openings. Insert the ducting into each opening 
and fix it in place using the 6 steel brackets supplied (3 for each duct). 
2.  Maintain at least a 2" (50 mm) clearance between the ducts and the firestop; the 
required hole size for the hot air grilles (outlet) is 8¼" × 8¼" (210 mm × 210 mm). 
3.  The maximum number of elbows in a run of duct is two. 
4.  Maintain at least 10" (254 mm) clearance from the outlet grille framing to a combustible 
ceiling, side wall or mantel. 
5.  When passing through a combustible wall or floor, a firestop must be installed at the 
wall or floor penetration. The hole size must be in accordance with the duct 
manufacturer’s instructions. 
6.  Do not connect the hot air ducts to a central heating system. Malfunction of the heating 
system’s fan will cause the fireplace to overheat. 
7.  Do not use insulated flexible ducts as they may overheat. 
8.  Do not use tees or any other components than the ones specifically listed here. 
9.  All ducts must extend upwards or horizontally. Never route the ducting downwards. 
10. The hot air outlet grilles must be installed with the louvers pointing downwards in order 
to prevent overheating adjacent ceilings. 
11. Always install the two outlet grilles when using the hot air outlet kit and blocking the 
upper louver of the fireplace. 